PROFIBUS Interface Center

SPC3

Page 18

V1.3

SPC3 Hardware Description

2003/04

Copyright (C) Siemens AG 2003. All rights reserved.

Bit 0

DIS_START_CONTROL

Monitoring the following start bit in UART. Set-Param Telegram overwrites this memory cell in
the DP mode. (Refer to the user-specific data.)

0 =

Monitoring the following start bit is enabled.

1 =

Monitoring the following start bit is switched off.

Bit 1

DIS_STOP_CONTROL

Stop bit monitoring in UART. Set-Param telegram overwrites this memory cell in the DP mode.
(Refer to the user-specific data.)

0 =

Stop bit monitoring is enabled.

1 =

Stop bit monitoring is switched off.

Bit 2

EN_FDL_DDB

Reserved

0 =

The FDL_DDB receive is disabled.

Bit 3

MinTSDR

Default setting for the MinTSDR after reset for DP operation or combi operation

0 =

Pure DP operation (default configuration!)

1 =

Combi operation

Bit 4

INT_POL

Polarity of the interrupt output

0 =

The interrupt output is low-active.

1 =

The interrupt output is high-active.

Bit 5

EARLY_RDY

Moved up ready signal

0 =

Ready is generated when the data are valid (read) or when the data are accepted
(write).

1 =

Ready is moved up by one clock pulse.

Bit 6

Sync_Supported

Sync_Mode support

0 =

Sync_Mode is not supported.

1 =

Sync_Mode is supported.

Bit 7

Freeze_Supported

Freeze_Mode support

0 =

Freeze_Mode is not supported.

1 =

Freeze_Mode is supported.

Bit 8

DP_MODE

DP_Mode enable

0 =

DP_Mode is disabled.

1 =

DP_Mode is enabled. SPC3 sets up all DP_SAPs.

Bit 9

EOI_Time base

Time base for the end of interrupt pulse

0 =

The interrupt inactive time is at least 1 usec long.

1 =

The interrupt inactive time is at least 1 ms long.

Bit 10

User_Time base

Time base for the cyclical User_Time_Clock-Interrupt

0 =

The User_Time_Clock-Interrupt occurs every 1 ms.

1 =

The User_Time_Clock-Interrupt occurs every 10 ms.

Bit 11

WD_Test

Test mode for the Watchdog-Timer, no function mode

0 =

The WD runs in the function mode.

1 =

Not permitted

Bit 12

Spec_Prm_Puf_Mode

Special parameter buffer

0 =

No special parameter buffer.

1 =

Special parameter buffer mode .Parameterization data will be stored directly in the
special parameter buffer.

Bit 13

Spec_Clear_Mode

Special Clear Mode (Fail Safe Mode)

0 =

No special clear mode.

1 =

Special clear mode. SPC3 will accept datea telegramms with data unit = 0.


Figure 5.1: Mode-Register 0 Bit 12 .. 0.(can be written to, can be changed in offline only)