Profibus interface center, Spc3 – Siemens SPC3 User Manual

Page 64

Advertising
background image

PROFIBUS Interface Center

SPC3

Page 62

V1.3

SPC3 Hardware Description

2003/04

Copyright (C) Siemens AG 2003. All rights reserved.


Identifier-Related Diagnostics:

For each identifier byte assigned during configuration (for example, 0 x 10 for 1 byte input), a bit is
reserved.

In the case of a modular system with an identifier byte each per module, module-specific diagnostics can be
indicated. One bit respectively will then indicate diagnostics per module.

Bit 7

Bit 6

Bit 5-0

Header Byte

0

1

Block length in bytes including header

Bit Structure

1

1

Identifier Byte 7 has

etc. Identifier Byte 0 has

diagnostics

diagnostics

Channel-Related Diagnostics:

In this block, the diagnosed channels and the diagnostics cause are entered in sequence. Three bits are
required per entry.

Bit 7

Bit 6

Bit 5

Bit 4 - 0

Header Byte

1

0

Identification Number

Channel Number

Coding
Input/Output

Channel Number

Type of Diagnostics

Coding
Channel Type

Coding
Error Type


Coding of the error type is in part manufacturer-specific; other codings are specified in the Standard.

Example:



Status

If the Bit EXT_DIAG is set to 0 , data is viewed as status info from the system view. f.e. cancellation of the
error triggering the diagnostics.

0 0 0 0 0 1 0 0 Device-related diagnostics.
Device-specific

Meaning of the bits

diagnostics field of

is specified

length 3

manufacturer-specific.

0 1 0 0 0 1 0 1 Identifier-related diagnostics.

1 Identification number 0 has diagnostics.

1

1

Identification number 18 has diagnostics.

1 0 0 0 0 0 0 0 Channel-related diagnostics, identification number 0.
0 0 0 0 0 0 1 0 Channel 2.

0 0 0 1 0 1 0 0 Overload, channel organized bit by bit.

1 0 0 0 1 1 0 0 Channel-related diagnostics identification number 12.
0 0 0 0 0 1 1 0 Channel 6.

1 0 1 0 0 1 1 1 Upper limit evalue xceeded, channel organized word by word.

Advertising