8-4. Freeze Prevention (Cooling)

This function prevents freezing of the indoor heat exchange coil.

When the compressor has been running for 10 minutes or more and the temperature of the indoor heat

exchange coil falls below 30°F, the control circuit stops the compressor for at least 6 minutes. The compressor

does not start again until the temperature rises above 46°F or 6 minutes has elapsed.

8-5. Overload Prevention (Heating)

This function prevents overheating of the indoor heat exchange coil.

When the temperature of the indoor heat exchange coil rises above 139°F, and if the indoor fan is L (low

speed), then the fan speed changes from L (low speed) to M (medium speed).

When the temperature of the indoor heat exchange coil rises above 141°F, the outdoor fan stops.

ON

ON

OFF

ON

H or M or L

H

H, M

M, L

M

141
139

126

120

Indoor heat
exch. coil
temp.

¡

F

Outdoor fan

Indoor fan

Compressor

ON

ON

ON

ON

OFF

OFF

Set speed

More than

10 minutes

6 minutes

T + 4

¡

F

Indoor heat exch.
coil temp.

30

¡

F

Compressor

Indoor fan

Room temp.

Thermo. OFF

Thermo. ON

Set temp. T

¡

F

More than

10 minutes

More than

6 minutes

Set speed

000-111

SM

(18-68)

00.3.17

11:49

AM

y [ W 50