7. defrosting operation (heating), Defrosting flowchart – Sanyo CH1852 User Manual

Page 56

Advertising
background image

52

8-7. Defrosting Operation (Heating)

Defrosting Flowchart

Compressor ON

Indoor heat exchanger coil
temperature drops 1.4

¡

F per

6 minutes and it repeats
3 times in succession.

Integrated operating time of
compressor is more than 3
hours.

Defrosting begins.

Cold-draft prevention

Temperature of outdoor heat
exchange coil is higher than
54

¡

F

.

Release of defrosting

Indoor fan runs at set speed
when temperature of indoor
heat exchanger reads 95

¡

F

.

B

Defrosting time is over 12
minutes.

Compressor keeps running
for at least 6 minutes.

Temperature of outdoor heat
exchanger coil is below 48

¡

F

.

Integrated operating time of
compressor is more than 1.5
hours.

Thermo. OFF.
(Compressor OFF)

C

D

Temperature of indoor heat
exchanger coil is below 113

¡

F

.

Temperature of indoor heat
exchanger coil is below 113

¡

F

.

Continuous operating time of
compressor is more than 20
minutes.

Outdoor fan is either operated
or stopped for more than 10
minutes.

A

Is outdoor fan continuously
operating for more than 10
minutes?

Integrated operating time of
compressor is more than 50
minutes.

Temperature of indoor heat
exchanger coil is below 113 +
23

¡

F

.

Temp. of indoor heat exch.
coil immediately before thermo
goes off is either below 113 + 7

¡

F

or 136 + 7

¡

F

(when overload

prevention works).

NO

NO

NO

YES

YES

YES

Overload

prevention works.

Does outdoor fan

stop?

Compressor keeps running for
at least 6 minutes.

Release of overload prevention
(Outdoor fan operates.)

Compressor keeps running for
at least 6 minutes.

000-111

SM

(18-68)

00.3.17

11:49

AM

y [ W 52