B-VENT GAS FIREPLACES • MODELS SLBV-35, SLBV-40 • INSTALLATION INSTRUCTIONS

Figure 2 - Dexen Electronic Gas Valve

Pilot Stage

Terminal

Pressure-Tap

(Inlet)

Pilot Gas

Outlet

Supply

Gas

Inlet

Pressure-Tap

(Manifold)

Burner Stage

Terminal

Ground

(TP)

PILOT

OUT

VENT

LO

TH TP

TH

TP

HI

IN

IN

Regulator

Mounting Screw

Test gauge connections are provided on the

front of the gas control valve, identified IN for

the inlet and OUT for the manifold side (see

Figures 1 and 2).

Propane tanks are at pressures that will cause

damage to valve components. Verify that the

tanks have step-down regulators to reduce the

pressure to safe levels.

GAS VALVE dIAGRAMS

See Figure 1 for millivolt models and Figure 2

for electronic models.

ORIfICE SIzES

Sea Level to High Altitude

(All Models)

These appliances are tested and approved for

installation at elevations of 0–4500 feet (0–1372

meters) above sea level using the standard

burner orifice sizes (marked with an asterisk

(*) in Table 4, below).

For elevations above 4500 feet, contact your

gas supplier or a qualified service technician.

deration

At higher elevations, the amount of BTU fuel

value delivered must be reduced by either:
• using gas that has been derated by the gas

company,

• changing the burner orifice to a smaller size

as regulated by the local authorities having

jurisdiction and by the (USA) National Fuel Gas

Code NFPA 54/ANSI Z223.1 - latest edition or,

in Canada, the CAN/CSA-B149.1 codes - latest

edition.

Install the appliance according to the regulations

of the local authorities having jurisdiction and,

in the USA, the National Fuel Gas Code NFPA

54 / ANSI Z223.1 - latest edition or, in Canada,

the CAN/CSA-B149.1 - latest edition.

NOTE: Flame appearance will diminish

4% per thousand feet of altitude.

Manifold Gas Supply Pressure

(All models)

fuel #

Low

High

Natural

Gas

(Lo) 2.2" WC

(0.55 kPa)

(Hi) 3.5" WC

(0.87 kPa)

Propane (Lo) 6.3" WC

(1.57 kPa)

(Hi) 10.0" WC

(2.49 kPa)

Table 3

REqUIREMENTS fOR THE

COMMONWEALTH Of

MASSACHUSETTS

These fireplaces are approved for installation in

the US state of Massachusetts if the following

additional requirements are met:
• Install this appliance in accordance with

Massachusetts Rules and Regulations 248

C.M.R.

• Installation and repair must be done by a

plumber or gas fitter licensed in the Com-

monwealth of Massachusetts.

• The flexible gas line connector used shall

not exceed 36 inches (92 centimeters) in

length.

• The individual manual shut-off must be a

T-handle type valve.

NEW YORK CITY APPROVAL

New York City, NY (MEA)
These fireplaces are approved for installation

in New York City in the US state of New York

if the following additional requirement is met:
• An Outside Combustion Air Kit (FOAK-4,

FOAK-4LD, or DK-4) must be installed. See

Step 5 on Page 14.

Inlet Gas Supply Pressure

(All models)

fuel #

Minimum

Maximum

Natural Gas

4.5" WC

(1.12 kPa)

10.5" WC

(2.61 kPa)

Propane

11.0" WC

(2.74 kPa)

13.0" WC

(3.23 kPa)

Table 2

GAS PRESSURE REqUIREMENTS

(All Models)
Tables 2 and 3
show the appliances' inlet and

manifold gas pressure requirements:

These appliances must be isolated

from the gas supply piping system (by

closing their individual manual shut-off

valve) during any pressure testing of

the gas supply piping system at test

pressures equal to or less than 1/2 psig

(3.5 kPa).
These appliances and their individual

shut-off valves must be disconnected

from the gas supply piping system

during any pressure testing of that

system at pressures greater than 1/2

psig (3.5 kPa).

Burner Orifice Sizes

Elevation 0-4500 feet ( 0-1372 meters)

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

SLBV-35

#48 (0.076")*

H1236•

#56 (0.046")*

62L37•

SLBV-40

#43 (0.089")*

99K75•

#55 (0.052")*

19L52•

Table 4

*

Standard size installed at factory.

Part /Catalog Number.

H I

LO

W

HT

PT

HT

PT

PILO

T

PI

LO

T

ON

it

OFF

IN

OUT

HI/LO Variable

flame Height

Adjustment

Figure 1 - SIT Millivolt Gas Valve

Manifold Pressure Tap

Inlet Pressure Tap

Pilot Adjustment

Screw

Main Gas Control Knob

Off/PILOT/ON

4

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.