Vent termination clearances – Superior SLBV-40PM User Manual

Page 6

Advertising
background image

Termination Heights for Vents

Above flat Or Sloped Roofs

Ref. NfPA 54 / ANSI z223.1

Roof Pitch

* feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

VENT TERMINATION

CLEARANCES

Multiple Terminations

These appliances may vent adjacent to and at

the same level with any other gas appliances

(including direct vent appliances), provided

there is at least 2 ft (0.6 m) between the proxi-

mal edges of the vent caps. These appliances

may be vented adjacent to a chimney vent

servicing a solid fuel fireplace, provided the

B-vent cap is at least 2 ft (0.6 m) away from the

nearest point of the chimney opening.

Gas Vent Rule

Gas vent caps are not permitted within 8 ft (2.4

m) of a vertical wall or similar obstruction. Gas

vent caps that are located 8 ft or more from a

portion of a building that extends at an angle

greater than 45° upward from the horizontal

may terminate in accordance with Figure 4,

provided that any discharge opening on

the cap is NEVER LESS THAN 2 ft (0.6 m)

horizontally from the roof surface (National

Fuel Gas Code ANSI Z223.1 (NFPA 54) “Gas

Vent Termination” section) (CAN/CGA B149.1).

Figure 4

Roof Pitch is X/12

Minimum Height from Roof to

Lowest discharge Opening

X

12

1" (25 mm)

Minimum

Gas Vent Rule

Table 5

SUPERIOR

®

B-VENT GAS FIREPLACES • MODELS SLBV-35, SLBV-40 • INSTALLATION INSTRUCTIONS

6

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.