Sterling AquaSnap 30RA010-055 User Manual

Page 27

Advertising
background image

27

Table 10 — Run Status Mode and Sub-Mode Directory

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

SUB-ITEM

DISPLAY

SUB-ITEM DISPLAY

ITEM

EXPANSION

COMMENT

VIEW

EWT

XXX.X

°F

ENTERING FLUID TEMP

LWT

XXX.X

°F

LEAVING FLUID TEMP

SETP

XXX.X

°F

ACTIVE SETPOINT

CTPT

XXX.X

°F

CONTROL POINT

LOD.F

XXX

LOAD/UNLOAD FACTOR

STAT

X

CONTROL MODE

0 = Service Test
1 = Off Local
2 = Off

SCN

3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On

SCN

7 = On Time
8 = Ht Enabled
9 = Pump Delay

LD.PM

LEAD PUMP

OCC

YES/NO

OCCUPIED

LS.AC

YES/NO

LOW SOUND ACTIVE

MODE

YES/NO

OVERRIDE MODES IN EFFECT

CAP

XXX %

PERCENT TOTAL CAPACITY

STGE

X

REQUESTED STAGE

ALRM

XXX

CURRENT ALARMS & ALERTS

TIME

XX.XX

TIME OF DAY

00.00-23.59

MNTH

XX

MONTH OF YEAR

1 = January, 2 = February, etc.

DATE

XX

DAY OF MONTH

01-31

YEAR

XX

YEAR OF THE CENTURY

RUN

HRS.U XXXX HRS

MACHINE OPERATING HOURS

STR.U

XXXX

MACHINE STARTS

HR.P1

XXXX.X

PUMP 1 RUN HOURS

HR.P2

XXXX.X

PUMP 2 RUN HOURS

HOUR

HRS.A XXXX HRS

CIRCUIT A RUN HOURS

HRS.B XXXX HRS

CIRCUIT B RUN HOURS

See Note

HR.A1 XXXX HRS

COMPRESSOR A1 RUN HOURS

HR.A2 XXXX HRS

COMPRESSOR A2 RUN HOURS

HR.B1 XXXX HRS

COMPRESSOR B1 RUN HOURS

See Note

HR.B2 XXXX HRS

COMPRESSOR B2 RUN HOURS

See Note

STRT

ST.A1

XXXX

COMPRESSOR A1 STARTS

ST.A2

XXXX

COMPRESSOR A2 STARTS

ST.B1

XXXX

COMPRESSOR B1 STARTS

See Note

ST.B2

XXXX

COMPRESSOR B2 STARTS

See Note

PM

PUMP

PUMP MAINTENANCE

SI.PM

XXXX HRS

PUMP SERVICE INTERVAL

P.1.DN

XXXX HRS

PUMP 1 SERVICE COUNTDOWN

P.2.DN

XXXX HRS

PUMP 2 SERVICE COUNTDOWN

P.1.MN

YES/NO

PUMP 1 MAINTENANCE DONE

User Entry

P.2.MN

YES/NO

PUMP 2 MAINTENANCE DONE

User Entry

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER