Table 10 — Run Status Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
SUB-ITEM
DISPLAY
SUB-ITEM DISPLAY
ITEM
EXPANSION
COMMENT
VIEW
EWT
XXX.X
°F
ENTERING FLUID TEMP
LWT
XXX.X
°F
LEAVING FLUID TEMP
SETP
XXX.X
°F
ACTIVE SETPOINT
CTPT
XXX.X
°F
CONTROL POINT
LOD.F
XXX
LOAD/UNLOAD FACTOR
STAT
X
CONTROL MODE
0 = Service Test
1 = Off Local
2 = Off
SCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On
SCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
LD.PM
LEAD PUMP
OCC
YES/NO
OCCUPIED
LS.AC
YES/NO
LOW SOUND ACTIVE
MODE
YES/NO
OVERRIDE MODES IN EFFECT
CAP
XXX %
PERCENT TOTAL CAPACITY
STGE
X
REQUESTED STAGE
ALRM
XXX
CURRENT ALARMS & ALERTS
TIME
XX.XX
TIME OF DAY
00.00-23.59
MNTH
XX
MONTH OF YEAR
1 = January, 2 = February, etc.
DATE
XX
DAY OF MONTH
01-31
YEAR
XX
YEAR OF THE CENTURY
RUN
HRS.U XXXX HRS
MACHINE OPERATING HOURS
STR.U
XXXX
MACHINE STARTS
HR.P1
XXXX.X
PUMP 1 RUN HOURS
HR.P2
XXXX.X
PUMP 2 RUN HOURS
HOUR
HRS.A XXXX HRS
CIRCUIT A RUN HOURS
HRS.B XXXX HRS
CIRCUIT B RUN HOURS
See Note
HR.A1 XXXX HRS
COMPRESSOR A1 RUN HOURS
HR.A2 XXXX HRS
COMPRESSOR A2 RUN HOURS
HR.B1 XXXX HRS
COMPRESSOR B1 RUN HOURS
See Note
HR.B2 XXXX HRS
COMPRESSOR B2 RUN HOURS
See Note
STRT
ST.A1
XXXX
COMPRESSOR A1 STARTS
ST.A2
XXXX
COMPRESSOR A2 STARTS
ST.B1
XXXX
COMPRESSOR B1 STARTS
See Note
ST.B2
XXXX
COMPRESSOR B2 STARTS
See Note
PM
PUMP
PUMP MAINTENANCE
SI.PM
XXXX HRS
PUMP SERVICE INTERVAL
P.1.DN
XXXX HRS
PUMP 1 SERVICE COUNTDOWN
P.2.DN
XXXX HRS
PUMP 2 SERVICE COUNTDOWN
P.1.MN
YES/NO
PUMP 1 MAINTENANCE DONE
User Entry
P.2.MN
YES/NO
PUMP 2 MAINTENANCE DONE
User Entry
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER