Table 24 — Example of Reading and Clearing Alarms

Table 25A — 4-20 mA Reset

NOTE: The example above shows how to configure the chiller for 4-20 mA reset. No reset will occur
at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required.

Table 25B — Menu Configuration of 4 to 20 mA Cooling Set Point Control

SUB-MODE

KEYPAD

ENTRY

ITEM

ITEM EXPANSION

COMMENT

CRNT

AXXX or TXXX

CURRENTLY ACTIVE ALARMS

ACTIVE ALARMS (AXXX) OR
ALERTS (TXXX) DISPLAYED.

CRNT

RCRN

NO

Use to clear active alarms/alerts

NO

NO Flashes

YES

Select YES

NO

Alarms/alerts clear, YES changes to NO

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

ITEM

EXPANSION

COMMENT

RSET

CRST

1

COOLING RESET

TYPE

0 = no reset
1 = 4 to 20 mA input
2 = Outdoor air temp
3 = Return Fluid
4 = Space Temperature

CRT1

4.0

NO COOL RESET

TEMP

Default: 125 F (51.7 C)
Range: 0° to 125 F

CRT2

20.0

FULL COOL

RESET TEMP

Default: 0° F (–17.8 C)
Range: 0° to 125 F

DGRC

5.0 F

(2.8 C)

DEGREES COOL

RESET

Default: 0° F (0° C) Reset at 20 mA
Range: –30 to 30 F (–16.7 to 16.7 C)

MODE

(RED LED)

KEYPAD

ENTRY

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

ITEM

EXPANSION

COMMENT

CONFIGURATION

DISP

UNIT

OPT1

OPT2

RSET

SLCT

CLSP

0

COOLING SETPOINT SELECT

0

Scrolling Stops

0

Flashing ‘0’

4

Select ‘4’

4

Change Accepted

ENTER

ESCAPE

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER