RESETCON (Temperature Reset and Demand Limit)

SCHEDOVR (Timed Override Setup)

SETPOINT

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

COOLING RESET

Cooling Reset Type

0 = No Reset
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT

0

CRST_TYP

4-20 MA RESET

4-20 – Degrees Reset

–30 to 30

0.0

∆∆∆∆F

420_DEG

REMOTE RESET

Remote – No Reset Temp

0 to 125

125.0

°°°°F

REM_NO

Remote – Full Reset Temp

0 to 125

0.0

°°°°F

REM_FULL

Remote – Degrees Reset

–30 to 30

0.0

∆∆∆∆F

REM_DEG

RETURN TEMPERATURE RESET
Return – No Reset Temp

0 to 125

10.0

∆∆∆∆F

RTN_NO

Return – Full Reset Temp

0 to 125

0.0

∆∆∆∆F

RTN_FULL

Return – Degrees Reset

–30 to 30

0.0

∆∆∆∆F

RTN_DEG

DEMAND LIMIT

Demand Limit Select

0 = None
1 = External switch input
2 = 4-20 mA input
3 = Loadshed

0

DMD_CTRL

Demand Limit at 20 mA

0 to 100

100

%

DMT20MA

Loadshed Group Number

0 to 99

0

SHED_NUM

Loadshed Demand Delta

0 to 60

0

%

SHED_DEL

Maximum Loadshed Time

0 to 120

60

minutes

SHED_TIM

Demand Limit Switch 1

0 to 100

80

%

DLSWSP1

Demand Limit Switch 2

0 to 100

50

%

DLSWSP2

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Schedule Number

0 to 99

1

SCHEDNUM

Override Time Limit

0 to 4

0

hours

OTL

Timed Override Hours

0 to 4

0

hours

OVR_EXT

Timed Override

No/Yes

No

TIMEOVER

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

COOLING

Cooling Setpoint 1

–20 to 70

44.0

°°°°F

CSP1

Cooling Setpoint 2

–20 to 70

44.0

°°°°F

CSP2

ICE Setpoint

–20 to 32

32.0

°°°°F

CSP3

RAMP LOADING

Cooling Ramp Loading

0.2 to 2.0

1.0

CRAMP

Brine Freeze Point

–20 to 34

34.0

°°°°F

BRN_FRZ