Sterling AquaSnap 30RA010-055 User Manual
Page 32

32
Table 17 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
OPT1
UNIT OPTIONS 1 HARDWARE
FLUD
X
COOLER FLUID
Default: Water
1 = Water
2 = Medium Temperature Brine
MLV.S
YES/NO
MINIMUM LOAD VALVE SELECT
MMR.S
YES/NO
MOTORMASTER SELECT
RG.EN
ENBL/DSBL
RETURN GAS SENSOR ENABLE
Default: DISABLED
CPC
ON/OFF
COOLER PUMP CONTROL
Default: On
PM1E
YES/NO
COOLER PUMP 1 ENABLE
PM2E
YES/NO
COOLER PUMP 2 ENABLE
PM.P.S
YES/NO
COOLER PMP PERIODIC STRT
Default: No
PM.SL
X
COOLER PUMP SELECT
Default: Automatic
0 = Automatic
1 = Pump 1 Starts first
2 = Pump 2 Starts first
PM.DY
XX MIN
COOLER PUMP SHUTDOWN DLY
0 to 10 minutes, Default: 1 min.
PM.DT
XXXX HRS
PUMP CHANGEOVER HOURS
Default: 500 hours
ROT.P
YES/NO
ROTATE COOLER PUMPS NOW
User Entry
EMM
YES/NO
EMM MODULE INSTALLED
OPT2
UNIT OPTIONS 2 CONTROLS
CTRL
X
CONTROL METHOD
Default: Switch
0 = Enable/Off/Remote Switch
2 = Occupancy
3 =
SCN Control
SCNA XXX SCN ADDRESS Default: 1
Range: 1 to 239
SCNB XXX SCN BUS NUMBER Default: 0
Range: 0 to 239
BAUD X
SCN BAUD RATE Default: 9600
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
LOAD
X
LOADING SEQUENCE SELECT
Default: Equal
1 = Equal
2 = Staged
LLCS
X
LEAD/LAG CIRCUIT SELECT
Default: Automatic
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT
XX.X
∆F
HIGH LCW ALERT LIMIT
Default: 60
Range: 2 to 60
°F
DELY
XX
MINUTES OFF TIME
Default: 0 Minutes
Range: 0 to 15 Minutes
ICE.M
ENBL/DSBL
ICE MODE ENABLE
Default: Disable
CLS.C
ENBL/DSBL
CLOSE CONTROL SELECT
Default: Disable
LS.MD
X
LOW SOUND MODE SELECT
Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
LS.ST
00:00
LOW SOUND START TIME
Default: 00:00
LS.ND
00:00
LOW SOUND END TIME
Default: 00:00
LS.LT
XXX %
LOW SOUND CAPACITY LIMIT
Default: 100%
Range: 0 to 100%
RSET
RESET COOL TEMP
CRST
X
COOLING RESET TYPE
Default: No Reset
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
MA.DG
XX.X
∆F
4-20 - DEGREES RESET
Default: 0.0
∆F
Range: –30 to 30
∆F
RM.NO
XXX.X
°F
REMOTE - NO RESET TEMP
Default: 125
F (51.7 C)
Range: 0° to 125
F
ENTER
ENTER
ENTER