START-UP CHECKLIST FOR 30RA LIQUID CHILLER

(Remove and use for Job File)

I. Project Information

JOB NAME

______________________________________________________________________________

ADDRESS _______________________________________________________________________________

CITY

____________________________________________ STATE _______________ ZIP______________

INSTALLING CONTRACTOR

________________________________________________________________

SALES OFFICE ___________________________________________________________________________

START-UP PERFORMED BY

________________________________________________________________

Design Information

UNIT MODEL ______________________________ SERIAL ________________________________

II. Preliminary Equipment Check

IS THERE ANY PHYSICAL DAMAGE?



YES



NO

DESCRIPTION ____________________________________________________________________________

________________________________________________________________________________________

1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS.



YES



NO

2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE.



YES



NO

3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY.



YES



NO

4. UNIT IS PROPERLY GROUNDED.



YES



NO

5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY.



YES



NO

6. ALL TERMINALS ARE TIGHT.



YES



NO

7. ALL PLUG ASSEMBLIES ARE TIGHT.



YES



NO

8. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES.



YES



NO

9. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS.



YES



NO

Chilled Water System Check

1. ALL CHILLED WATER VALVES ARE OPEN.



YES



NO

2. ALL PIPING IS CONNECTED PROPERLY.



YES



NO

3. ALL AIR HAS BEEN PURGED FROM THE SYSTEM.



YES



NO

4. CHILLED WATER PUMP IS OPERATING WITH THE CORRECT ROTATION.



YES



NO

CAPACITY

CEAT

EWT

LWT

FLUID TYPE

FLOW RATE

P.D.