CL-2

5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.



YES



NO

6. CHILLED WATER FLOW SWITCH IS OPERATIONAL.



YES



NO

7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40).



YES



NO

8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C).



YES



NO

ANTIFREEZE TYPE _____________________ CONCENTRATION __________%.
IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 9-11 HAVE TO BE
COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER
TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.)

9. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE,



YES



NO

INSULATED AND OPERATIONAL.

10. COOLER HEATERS INSTALLED AND OPERATIONAL.



YES



NO

11. CHILLED WATER PUMP CONTROLLED BY CHILLER.



YES



NO

III. Unit Start-Up

1. COMPRESSOR OIL LEVEL IS CORRECT.



YES



NO

2. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 10-14 FT-LB. (13.5-18.9 N-M).



YES



NO

3. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS.



YES



NO

4. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE.



YES



NO

5. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE.



YES



NO

6. CONTROL TRANSFORMER SECONDARY VOLTAGE =

7. CHECK VOLTAGE IMBALANCE:

A-B

A-C

B-C

AVERAGE VOLTAGE =

(A-B + A-C + B-C)/3

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100
VOLTAGE IMBALANCE LESS THAN 2%.



YES



NO

(DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%.
CONTACT LOCAL UTILITY FOR ASSISTANCE.)

8. VERIFY COOLER FLOW RATE.



YES



NO

PRESSURE ENTERING COOLER

________ psig (kPa)

PRESSURE LEAVING COOLER

________ psig (kPa)

COOLER PRESSURE DROP

________ psig (kPa)

Psig X 2.31 ft./psi =

________ ft of water

kPa X 0.334 m/psi

________ m of water

COOLER FLOW RATE

________ gpm (l/s) (See Cooler Pressure

Drop Curves from
Installation, Start-up and
Service Instructions)

Start and Operate Machine. Complete the Following:

1. COMPLETE COMPONENT TEST.



YES



NO

2. CHECK REFRIGERANT AND OIL CHARGE.

 YES



NO

3. RECORD COMPRESSOR MOTOR CURRENT.



YES



NO

4. RECORD CONFIGURATION SETTINGS.



YES



NO

5. RECORD OPERATING TEMPERATURES AND PRESSURES.



YES



NO

6. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL.

Instruction Time ________ hours.