56 table 29 — alarm and alert codes (cont) – Sterling AquaSnap 30RA010-055 User Manual

Page 56

Advertising
background image

56

Table 29 — Alarm and Alert Codes (cont)

ALARM/

ALERT

CODE

ALARM

OR

ALERT

DESCRIPTION

WHY WAS THIS

ALARM

GENERATED?

ACTION TAKEN

BY CONTROL

RESET

METHOD

PROBABLE

CAUSE

T196

Alert

Flow Lost While Pump 1
Running

Cooler flow switch contacts
open for 3 seconds after
initially made

All compressors
shut down. Pump 1
turned off. Pump 2 will
be started if available.
Chiller allowed to run if
Pump 2 successfully
starts and flow switch
is closed.

Manual

Wiring error, pump
circuit breaker
tripped, contactor fail-
ure

T197

Alert

Flow Lost While Pump 2
Running

Cooler flow switch contacts
open for 3 seconds after
initially made

All compressors shut
down. Pump 2 turned
off. Pump 1 will be
started if available.
Chiller allowed to run if
Pump 1 successfully
starts and flow switch
is closed.

Manual

Wiring error, pump
circuit breaker
tripped, contactor
failure

T198

Alert

Cooler pump 1 Aux
Contacts Closed While
Pump Off

Pump 1 Auxiliary Contacts
closed for 26 seconds
when pump state is off

Chiller not allowed to
start

Automatic when
aux contacts open

Wiring error, faulty
pump contactor
(welded contacts)

T199

Alert

Cooler pump 2 Aux
Contacts Closed While
Pump Off

Pump 2 Auxiliary Contacts
closed for 26 seconds
when pump state is off

Chiller not allowed to
start

Automatic when
aux contacts open

Wiring error, faulty
pump contactor
(welded contacts)

T200

Alert

Cooler Flow/Interlock
Contacts failed to Close
at start-up

Cooler flow switch contacts
failed to close within
1 minute (if cooler pump
control is enabled) or
within 5 minutes (if cooler
pump control is not
enabled) after start-up

Chiller not allowed to
start. For models with
dual pumps, the
second pump will be
started if available

Manual

Wiring error, pump
circuit breaker
tripped, contactor
failure, faulty flow
switch or interlock

A201

Alarm

Cooler Flow/Interlock
Contacts Opened
During Normal
Operation

Flow switch opens for at
least 3 seconds after
being initially closed

All compressors shut
down. For models with
dual pumps, the
second pump will be
started if available

Manual

Cooler pump failure,
faulty flow switch or
interlock, pump
circuit breaker
tripped

A202

Alarm

Cooler Pump Interlock
Closed When Pump is
Off

If configured for cooler
pump control and flow
switch input is closed for
5 minutes while pump
output(s) are off

Chiller shut down

Automatic when
aux contacts open

Wiring error, faulty
pump contactor
(welded contacts)

T203

Alert

Loss of Communication
with slave chiller

Master chiller MBB
loses communication
with slave chiller MBB

Dual chiller control
disabled. Chiller runs
as a stand-alone
machine.

Automatic

Wiring error, faulty
wiring, failed Slave
chiller MBB module,
power loss at slave
chiller, wrong slave
address.

T204

Alert

Loss of Communication
with master chiller

Slave chiller MBB loses
communication with
master chiller MBB

Dual chiller control
disabled. Chiller runs
as a stand-alone
machine

Automatic

Wiring error, faulty
wiring, failed master
chiller MBB module,
power loss at Master
chiller.

T205

Alert

Master and slave chiller
with same address

Master and slave chiller
have the same

SCN

address (

SCN.A)

Dual chiller routine
disabled. Master/slave
run as stand-alone
chillers.

Automatic

SCN Address for
both chillers is the
same. Must be
different. Check

SCN.A under the
OPT2 sub-mode in
Configuration at both
chillers.

T206

Alert

High Leaving Chilled
Water Temperature

LWT read is greater than
LCW Alert Limit, Total
capacity is 100% and LWT
is greater than LWT
reading one minute ago

Alert only. No action
taken.

Automatic

Building load greater
than unit capacity,
low water/brine flow
or compressor fault.
Check for other
alarms/alerts.

A207

Alarm

Cooler Freeze
Protection

Cooler EWT or LWT is less
than Brine Freeze (BR.FZ)

Chiller shutdown
without going through
pumpdown. Cooler
pump continues to
run a minimum of
5 minutes (if control
enabled).

Both EWT and LWT
must be at least 6 F
(3.3 C) above Brine
Freeze point (BR.FZ).
Automatic for first,
Manual reset thereaf-
ter.

Faulty thermistor
(T1/T2), low water
flow.

A208

Alarm

EWT or LWT
Thermistor failure

Cooler EWT is less than
LWT by 3° F (1.7° C) for
1 minute after a circuit is
started

Chiller shutdown.
Cooler pump shut off
(if control enabled).

Manual

Faulty cooler pump,
low water flow,
plugged fluid strainer.

T300

Alert

Cooler Pump 1
Scheduled
Maintenance Due

Pump 1 Service
Countdown (P.1.DN)
expired. Complete pump 1
maintenance and enter
'YES' for Pump 1
Maintenance Done
(P.1.MN) item.

None

Automatic

Routine pump
maintenance
required