Sterling AquaSnap 30RA010-055 User Manual
Page 47

47
Table 28 — Troubleshooting
SYMPTOMS
CAUSE
REMEDY
Cooler Circulating Pump Does
Not Run
Power line open
Reset circuit breaker.
Control fuse or circuit breaker open
Check control circuit for ground or short. Reset
breaker and replace fuse.
Compressor over temperature sensor open (06D)
Find cause of high temperature and reset controls.
Tripped power breaker
Check the controls. Find the cause of trip and reset
breaker.
Cooler circulating pump not running
Power off — restart.
Pump binding — free pump.
Incorrect wiring —rewire.
Pump motor burned out — replace.
Loose terminal connection
Check connections.
Improperly wired controls
Check wiring and rewire if necessary.
Low line voltage
Check line voltage — determine location of
voltage drop and remedy deficiency.
Compressor motor defective
Check motor winding for open or short.
Replace compressor if necessary.
Seized compressor
Replace compressor.
Compressor Cycles
Off on Loss of Charge
Loss of charge control erratic in action
Repair leak and recharge.
Replace control.
Low refrigerant charge
Add refrigerant.
Low suction temperature
Raise cooler leaving fluid temperature set point.
Compressor Cycles Off on Out
of Range Condition
Thermistor failure
Replace thermistor.
System load was reduced faster than controller
could remove stages
Unit will restart after fluid temperature rises back into
the control band. Avoid rapidly removing system
load.
Temperature controller deadband setting is too low
Raise deadband setting.
Compressor Shuts Down on
High-Pressure Control
High-pressure control acting erratically
Replace control.
Compressor discharge valve partially closed
Open valve or replace (if defective).
Noncondensables in system
Purge system.
Condenser scaled/dirty
Clean condenser.
Condenser water pump or fans not operating
Start pump — repair or replace if defective.
System overcharged with refrigerant
Reduce charge.
Unit Operates Too Long
or Continuously
Low refrigerant charge
Add refrigerant.
Control contacts fused
Replace control.
Air in system
Purge system.
Partially plugged or plugged expansion valve or filter
drier
Clean or replace as needed.
Defective insulation
Replace or repair as needed.
Service load
Keep doors and windows closed.
Inefficient compressor
Check valves, and replace if necessary.
Unusual or Loud System
Noises
Piping vibration
Support piping as required.
Check for loose pipe connections
Expansion valve hissing
Add refrigerant.
Check for plugged liquid line filter drier.
Compressor noisy
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.
Compressor Loses Oil
Leak in system
Repair leak.
Mechanical damage (Failed seals or broken scrolls)
Replace compressor.
Oil trapped in line
Check piping for oil traps.
Hot Liquid Line
Shortage of refrigerant due to leak
Repair leak and recharge.
Frosted Liquid Line
Shutoff valve partially closed or restricted
Open valve or remove restriction.
Restricted filter drier
Replace filter drier.
Frosted Suction Line
Expansion valve admitting excess refrigerant (note:
this is a normal condition for brine applications)
Adjust expansion valve. Replace valve if defective.
Freeze-Up
Improper charging
Make sure a full quantity of fluid is flowing through
the cooler while charging, and suction pressure in
cooler is equal to or greater than pressure corre-
sponding to 32 F (0° C) (58 psig [400 kPa] for
Refrigerant 22).
System not drained for winter shutdown
Recommended that system be filled with an appro-
priate glycol mixture to prevent freezing of pumps
and fluid tubing.
Loose Thermistor
Verify thermistors are fully inserted in wells.