Sterling AquaSnap 30RA010-055 User Manual

Page 47

Advertising
background image

47

Table 28 — Troubleshooting

SYMPTOMS

CAUSE

REMEDY

Cooler Circulating Pump Does
Not Run

Power line open

Reset circuit breaker.

Control fuse or circuit breaker open

Check control circuit for ground or short. Reset
breaker and replace fuse.

Compressor over temperature sensor open (06D)

Find cause of high temperature and reset controls.

Tripped power breaker

Check the controls. Find the cause of trip and reset
breaker.

Cooler circulating pump not running

Power off — restart.

Pump binding — free pump.

Incorrect wiring —rewire.
Pump motor burned out — replace.

Loose terminal connection

Check connections.

Improperly wired controls

Check wiring and rewire if necessary.

Low line voltage

Check line voltage — determine location of
voltage drop and remedy deficiency.

Compressor motor defective

Check motor winding for open or short.
Replace compressor if necessary.

Seized compressor

Replace compressor.

Compressor Cycles
Off on Loss of Charge

Loss of charge control erratic in action

Repair leak and recharge.
Replace control.

Low refrigerant charge

Add refrigerant.

Low suction temperature

Raise cooler leaving fluid temperature set point.

Compressor Cycles Off on Out
of Range Condition

Thermistor failure

Replace thermistor.

System load was reduced faster than controller
could remove stages

Unit will restart after fluid temperature rises back into
the control band. Avoid rapidly removing system
load.

Temperature controller deadband setting is too low

Raise deadband setting.

Compressor Shuts Down on
High-Pressure Control

High-pressure control acting erratically

Replace control.

Compressor discharge valve partially closed

Open valve or replace (if defective).

Noncondensables in system

Purge system.

Condenser scaled/dirty

Clean condenser.

Condenser water pump or fans not operating

Start pump — repair or replace if defective.

System overcharged with refrigerant

Reduce charge.

Unit Operates Too Long
or Continuously

Low refrigerant charge

Add refrigerant.

Control contacts fused

Replace control.

Air in system

Purge system.

Partially plugged or plugged expansion valve or filter
drier

Clean or replace as needed.

Defective insulation

Replace or repair as needed.

Service load

Keep doors and windows closed.

Inefficient compressor

Check valves, and replace if necessary.

Unusual or Loud System
Noises

Piping vibration

Support piping as required.

Check for loose pipe connections

Expansion valve hissing

Add refrigerant.

Check for plugged liquid line filter drier.

Compressor noisy

Replace compressor (worn bearings).
Check for loose compressor holddown bolts.

Compressor Loses Oil

Leak in system

Repair leak.

Mechanical damage (Failed seals or broken scrolls)

Replace compressor.

Oil trapped in line

Check piping for oil traps.

Hot Liquid Line

Shortage of refrigerant due to leak

Repair leak and recharge.

Frosted Liquid Line

Shutoff valve partially closed or restricted

Open valve or remove restriction.

Restricted filter drier

Replace filter drier.

Frosted Suction Line

Expansion valve admitting excess refrigerant (note:
this is a normal condition for brine applications)

Adjust expansion valve. Replace valve if defective.

Freeze-Up

Improper charging

Make sure a full quantity of fluid is flowing through
the cooler while charging, and suction pressure in
cooler is equal to or greater than pressure corre-
sponding to 32 F (0° C) (58 psig [400 kPa] for
Refrigerant 22).

System not drained for winter shutdown

Recommended that system be filled with an appro-
priate glycol mixture to prevent freezing of pumps
and fluid tubing.

Loose Thermistor

Verify thermistors are fully inserted in wells.

Advertising