Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 141

Advertising
background image

Altivar

®

58 TRX AC Drives

Suggested Specifications

141

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

f.

There will be 2 analog inputs. 1 analog input will be software selectable and consist of the following
configurations: 0-20 ma, 4-20 ma, 20-4 ma, x-20 ma (where x is user defined). The other analog
input shall be 0-10 Vdc.

g. There will be 4 isolated logic inputs, 3 shall be user assignable in the software. The selection of

assignments, at a minimum, shall consist of run, reverse, jog, ramp switching, plus/minus speed (2
inputs required), setpoint memory, preset speeds (up to 8 speeds), auto/manual control, fast stop,
forced local, motor switching, and fault reset.

h. One voltage-free Form C relay output contacts will be provided to indicate AC drive fault status. An

additional NO relay contact will be user assignable.

i.

There will be one analog output as standard that will be software selectable from 0–20 mA or
4–20 mA to represent a signal proportional to one of the following: motor current, motor speed,
± torque, motor power, PI loop variables, drive or motor thermal states.

j.

There shall be available an additional hardware input/output extension card which also provides
interlocking and sequencing capabilities. The card shall be fully isolated with pull apart terminal
strips. The analog output assignments shall be proportional to the following motor characteristics:
frequency, current, power, torque, and thermal state. The output signal will be selectable from 0-20
ma or 4-20 ma. All of the I/O will be user assignable in the software as previously defined.

2.11 Braking (Application-dependent Option)

NOTE: When braking certain types of loads, there is the conversion of kinematic energy into electrical
energy by the motor which is returned to the AC drive. Dynamic braking can be chosen to absorb this
energy and avoid causing the AC drive to inadvertently shut down. The energy is dissipated across a
resistor that is connected to the drive. For constant torque AC drives, the dynamic braking unit must be
capable of stopping 1.5 per unit motor torque from base frequency to 0.5 Hz with sensorless flux vector
control mode.

a. The dynamic brake resistor shall be provided and connect to existing terminals on the AC drive. The

resistor shall mount externally to the AC drive enclosure. A power transistor will be provided in the
AC drive to switch the excess energy to the braking resistor. The braking resistor will be of a size
calculated to stop 6 times motor inertia at 1.5 per unit motor torque.

2.12 HARMONIC ANALYSIS

NOTE: The amount of harmonic distortion at the point of common coupling (PCC) is due to the
distribution system characteristics (impedance of the source) and the power source size relative to the
AC drive load. The harmonic current magnitude and voltage distortion values can be predicted through
computer modeling. If the resulting calculations determine that the harmonic distortion will be above the
IEEE-519 specifications of 5%, isolation transformers or line reactors can be supplied to lower the
harmonic levels. The isolation transformers or line reactors are mounted at the AC drive input to reduce
the current harmonics that are fed back into the supply.

a. A harmonic analysis shall be performed and priced as a separate line item by the AC drive

manufacturer based upon system documentation consisting of but not limited to one-line diagrams
and specific distribution transformer information consisting of X/R,%Z, and kVA data. The data shall
consist of but not be limited to total harmonic voltage distortion and total rms current.

b. The maximum allowable input line unbalance shall be [5% for 460 V input line short circuit capacity

of 15,000 amps] [2.5% for 460 V input line short circuit capacity of 30,000 amps] [.5% for 460 V input
line short circuit capacity of 65,000 amps]. If the resulting voltage harmonic distortion exceeds 5%,
three phase, line reactor(s) shall be priced as a separate line item.

c. The line reactor(s) if required shall be provided in stand-alone Type 1 enclosures for mounting

separately from the AC drive.

Advertising
This manual is related to the following products: