Description of power terminals, Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual
Page 20: Power terminal wire size and torque, Atv58 trx power terminals
Altivar
®
58 TRX AC Drives
Description of Power Terminals
©
2000–2003 Schneider Electric All Rights Reserved
20
09/2003
DESCRIPTION OF POWER TERMINALS
As shown in the drawing to the left, the ATV58 TRX power terminal
arrangements differ from model to model. The locations of the power
terminals are shown on pages 18–19. The following tables describe the
characteristics of the power terminals and list maximum wire sizes and
tightening torques for the various ATV58 TRX models.
CONDUIT CONNECTIONS FOR TYPE E AND TYPE F
DRIVE CONTROLLERS
The ATV58 TRX Type E and Type F drive controllers are furnished with four
conduit openings at the bottom of the device. The conduit openings are
closed with Type 1 rated plugs. The holes are intended for input and output
power wiring, control wiring, and connection to external components such as
DB resistors or line reactors. To maintain the enclosure rating, do not remove
the plugs from unused conduit holes. Conduit holes are pre-drilled for the
conduit listed in the table below.
Flexible conduit must be used up to the drive controller to facilitate removal
of the terminal block cover. A minimum of 2 feet is recommended.
Function of Power Terminals
Terminal
Function
Found On
Ground terminal (2 provided on some models). All ATV58 TRX models.
L1
L2
Input power.
All models.
L3
All models except U09M2• and U18M2•
+
–
Connection for DB module.
Models U09M2• and U18M2•.
PA
PB
Connection for DB resistor.
All models except U09M2•, U18M2•, and
C10N4–C33N4.
U
V
W
Output connections to motor.
All models.
K13
K14
N.O. auxiliary contact on controller’s output
contactor. Maximum rating is 10 A at 600 Vac.
ATV58EU09M2ZU – U90N4FZ4.
Power Terminal Wire Size and Torque
Type FVC, Type H, and Type N Models
Maximum Wire Size
◆
AWG (mm
2
)
Torque
lb-in (N•m)
U09M2, U18M2
14 (1.5)
5.0 (0.55)
U29M2, U41M2, U18N4, U29N4, U41N4
8 (6)
7.5 (0.85)
U54M2, U72M2, U54N4, U72N4, U90N4
8 (6)
7.5 (0.85)
U90M2, D12M2, D12N4, D16N4, D23N4
6 (10)
20 (2.25)
D16M2, D23M2, D28N4, D33N4, D46N4
2/0 (35)
88 (10)
D28M2, D33M2, D46M2, D54N4, D64N4, D79N4
4/0 (70)
170 (19)
C10N4X–C19N4X
500 MCM
375 (42)
C23N4X–C33N4X
Supply crimp style lugs to fit selected wire size.
Type E and Type F Models
All models
10 (4)
5.0 (0.55)
◆
75 °C copper.
Type E and Type F Models
Conduit Hole Size
Conduit Size
Hub Catalog No.
ATV58EU09M2ZU
ATV58EU18M2ZU
7/8 inch
1/2 inch
25211-16102
All other ATV58 Type E and Type F
Drive Controllers
1 and 3/32 inch
3/4 inch
25211-24102
L1 L2
+
–
U
V W
ATV58*U09M2 - U18M2
L1 L2 L3 PA PB U
V W
ATV58*U29M2 - D12M2
ATV58*U18N4 - D23N4
P
o
wrT
e
rm
sNe
w
.eps
J2B
J2A
ATV58EU09M2ZU and ATV58EU18M2ZU
(single-phase input only)
U
V
W K13 K14 +
–
2
3
4
5
6
7
8
1
3
2
*
L2 L1
1
L3
* L3 is not used
J2B
J2A
ATV58Exxxxxxx
U
V
W K13 K14 PA PB
2
3
4
5
6
7
8
1
3
2
4
L2 L1
1
L3
ATV58*D16M2 - D46M2
ATV58*U28N4 - D79N4
+
–
L1 L2 L3
PA PB U
V W
ATV58HC10N4X
PA
U
L1 L2 L3
V W
PA
(+)
PC
(–)
ATV58HC13N4X–C19N4X
U
V
W
L2 L3
L1
PA
(+)
PC
(–)
ATV58HC23N4X–C33N4X
U
V
W
L2 L3
L1
PA
(+)
PC
(–)
PA
ATV58 TRX Power Terminals