Altivar

®

58 TRX AC Drives

Communication Parameters

©

2000–2003 Schneider Electric All Rights Reserved

84

09/2003

W294
or 16#5FE5/2D

TA2

1%

Rounding of the end of the acceleration ramp

0 to (100% of ramp time – TA1)

W295
or 16#5FE5/2E

TA3

1%

Rounding of the start of the deceleration ramp

0 to 100% of ramp time

W296
or 16#5FE5/2F

TA4

1%

Rounding of the end of the deceleration ramp

0 to (100% of ramp time – TA3)

W297
or 16#5FE5/30

SPG

1%

PI type speed loop proportional gain

0 to 1000

W298
or 16#5FE5/31

SIG

1%

PI type speed loop integral gain

0 to 1000

W299
or 16#5FE5/32

REO

PID regulator reference offset

–999 to +999

W300
or 16#5FE5/33

PAL

1%

PID feedback alarm min. threshold

0 to 100%

W301
or 16#5FE5/34

PAH

1%

PID feedback alarm max. threshold

0 to 100%

W302
or 16#5FE5/35

PER

1%

PID error alarm max. threshold

0 to 100%

W303
or 16#5FE5/36

RDG

0.01

PID regulator derivative gain

0 to 10000 (0 to 100.00)

W304
or 16#5FE5/37

PSP

0.1 s

PID feedback filter time constant

0 to 100 (0 to 10.0)

W305
or 16#5FE5/38

PSR

1%

PID speed input multiplier ratio

0 to 100

W306
or 16#5FE5/39

PLR

1%

PID regulator deadband ratio

0 to 100

W307
or 16#5FE5/3A

PLB

0.1 Hz

PID regulator deadband threshold

0 to HSP

W308
or 16#5FE5/3B

PI2

1%

2nd preset PID reference

0 to 100

W309
or 16#5FE5/3C

PI3

1%

3rd preset PID reference

0 to 100

W310
or 16#5FE5/3D

PRG

PID regulator reference gain

–999 to +999

W311
or 16#5FE5/3E

JF2

0.1 Hz

Skip frequency 2
± 2.5 Hz around setpoint

0 to HSP

W312
or 16#5FE5/3F

JF3

0.1 Hz

Skip frequency 3
± 2.5 Hz around setpoint

0 to HSP

W313
or 16#5FE5/40

FFT

0.1 Hz

Frequency threshold for start of freewheel stop
during deceleration phase if STT (W79) = STN or
FST

0 to HSP

W314
or 16#5FE5/41

F2D

0.1 Hz

Second frequency threshold for signalling

LSP to HSP

W315
or 16#5FE5/42

DTD

1%

Drive thermal state threshold value

0–118%

W316
or 16#5FE5/43

SP8

0.1 Hz

Preset speed 8 (125–500 hp only)

LSP to HSP

W317
or 16#5FE5/44

NAR

1

Number of restart attempts

0–255

W318
or 16#5FE5/45

TAR

s

Time between auto restarts

0.1–999.9

Adjustment Registers (Continued)

Word

Code

Units

Description

Possible Values or Range

[1]

This parameter does not exist for ATV58 Type FVC drive controllers.