DRIVE SELECTION
Class 8839 Econoflex
ä
enclosed drives are tailored for commercial market specifications for pump and fan applications. To select,
identify the catalog number by Class, Type, and Modification(s) numbers as shown below.
Class
Type Number
Modifications
8839
58E
V
➀
➁
➂
➃
➄
➅
➆
➇
➈
➀
Product
Code
Enclosed Drive
58E
Econoflex
➁
Horsepower
Code
Rating at 208,
230, 460 Vac
C
1 HP
D
2 HP
E
3 HP
F
5 HP
G
7.5 HP
H
10 HP
J
15 HP
K
20 HP
L
25 HP
M
30 HP
N
40 HP
P
50 HP
Code
Rating at
460 Vac
Q
60 HP
R
75 HP
S
100 HP
➂
Enclosure Type
Code
Environment
Rating
A
Type 12K
G
Type 1
➃
Voltage Rating
Code
Voltage
2
208 Vac
3
230 Vac
4
460 Vac
➄
Application Type
Code
Torque
V
Variable Torque
➅
Device Type
Code
Power Circuit
W
Without Bypass
Y
With Bypass
[1]
➈
Misc. Options
Code
Feature
A09
Line Reactor
[2]
B09
Line Contactor
[3]
C09
3 to 15 PSI
Transducer
[4]
D09
Omit Keypad
[12]
E09
Smoke Purge
[5]
G09
22 kAIC UL
Coordinated
Rating
H09
Analog Card,
0 to 20 mA
output
[6]
J09
0 to 10 mA
Auto Speed
Reference
[13]
➇
Light Option
Code
Light Cluster
A08
Power ON, AFC Run,
AFC Fault, Auto
[7]
B08
Power ON, AFC Run,
AFC Fault, Bypass
[7,8]
C08
Power ON, AFC Run,
AFC Fault
[7,9]
➆
Control Option
Code
Controls
A07
Hand-Off-Auto, Speed Potentiometer
[10]
B07
Hand-Off-Auto, Start-Stop,
Speed Potentiometer
[10]
C07
Start-Stop, Speed Potentiometer
[11]
N07
None
Notes
1.
Includes AFC-Off-Bypass switch and Test-Normal switch.
2.
Line reactor (A09) is an option for 1 to 20 hp @ 460 V and 1 to 10 hp @ 208/230 V. Line
reactor (A09) is included with 25 to 100 hp @ 460 V and 15 to 50 hp @ 208/230 V.
3.
Line contactor (B09) is not compatible with Power Circuit W (Without Bypass).
4.
3 to 15 PSI Transducer (C09) is not compatible with control option C07 (Start-Stop, Speed
Potentiometer), H09 (Analog Card), or J09 (0 to 10 V Auto Speed Reference).
5.
Smoke purge E09 permits the motor to run at full speed.
6.
Analog card H09 is not compatible with 3 to 15 PSI Transducer (C09).
7.
Light Cluster A08, B08, and C08 cannot be selected together; select only one.
8.
Light Cluster B08 is not compatible with Power Circuit W (Without Bypass).
9.
Light Cluster C08 is not compatible with control option A07 (Hand-Off-Auto, Speed
Potentiometer) or control option B07 (Hand-Off-Auto, Start-Stop, Speed Potentiometer).
10.
Hand-Off-Auto switch with Off position for AFC fault reset.
11.
Control option C07 (Start-Stop, Speed Potentiometer) is not compatible with Power Circuit
Y (Bypass) or light cluster A08 or B08.
12.
Omit the Keypad D09, user must buy a keypad as a separate device to program the
controller.
13.
0-10 V Auto speed reference J09 is not compatible with 3 to 15 PSI Transducer (C09).