Altivar

®

58 TRX AC Drives

Communication Parameters

87

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

W459
or 16#5FE8/A

ETI

Drive controller internal status register no. 1

Bit 0 = 0: Write parameters authorized
Bit 0 = 1: Write parameters not authorized
(EEPROM saving in progress)
Bit 1 = 0: No parameter consistency check,
drive controller locked at stop
Bit 1 = 1: Parameter consistency check
Bit 2 = 0: Fault reset not authorized
Bit 2 = 1: Fault reset authorized
Bit 3 = 0: No motor fluxing in progress (Type FVC only)
Bit 3 = 1: Motor fluxing in progress (Type FVC only)
Bit 4 = 0: Motor stopped
Bit 4 = 1: Motor running
Bit 5 = 0: No DC injection
Bit 5 = 1: DC injection
Bit 6 = 0: Drive controller running in steady state
Bit 6 = 1: Drive controller running in transient state (ACC or DEC)
Bit 7 = 0: No thermal overload alarm
Bit 7 = 1: Thermal overload alarm
Bit 8 = 0: No alarm if excessive braking
Bit 8 = 1: Alarm if excessive braking
Bit 9 = 0: Drive controller not accelerating
Bit 9 = 1: Drive controller accelerating
Bit 10 = 0: Drive controller not decelerating
Bit 10 = 1: Drive controller decelerating
Bit 11 = 0: No current limit alarm
Bit 11 = 1: Current limit alarm
Bit 12: Reserved
Bit 14 = 0, Bit 13 = 0: Control via wired terminal strip
Bit 14 = 0, Bit 13 = 1: Control via keypad display
Bit 14 = 1, Bit 13 = 0: Control via standard serial link
Bit 14 = 1, Bit 13 = 1: Control via fast serial link
Bit 15 = 0: Forward direction of rotation requested (reference)
Bit 15 = 1: Reverse direction of rotation requested (reference)

W460
or 16#5FE8/B

ETI2

Drive controller internal status register no. 2

Bit 0 = 0: Drive controller not in factory autotest mode
Bit 0 = 1: Drive controller in factory autotest mode
Bit 1 = 0: Drive controller not in board test mode
Bit 1 = 1: Drive controller in board test mode
Bit 2 = 0: Drive controller not in product test mode
Bit 2 = 1: Drive controller in product test mode (burn-in)
Bit 3 = 0: High speed not reached
Bit 3 = 1: High speed reached
Bit 4 = 0: Speed reference not reached
Bit 4 = 1: Speed reference reached
Bit 5 = 0: Frequency threshold (FTD) not reached
Bit 5 = 1: Frequency threshold (FTD) reached
Bit 6 = 0: Current threshold (CTD) not reached
Bit 6 = 1: Current threshold (CTD) reached
Bit 7 = 0: PID feedback correct (Type FVC only)
Bit 7 = 1: PID feedback exceeded (Type FVC only)
Bit 8 = 0: PID error correct (Type FVC only)
Bit 8= 1: PID error exceeded (Type FVC only)
Bit 9 = 0: 4–20 mA signal OK
Bit 9 = 1: Loss of 4–20 mA signal
Bit 10 = 0: No drive thermal alarm
Bit 10 = 1: Drive thermal alarm
Bits 11 to 15: Reserved

W461
or 16#5FE8/C

ETI3

Drive controller internal status register no. 3

Bit 0 = 0: Drive controller power does not exceed 7.5 kW @ 230 V or 15
kW @ 400 V
Bit 0 = 1: Drive controller power exceeds 7.5 kW @ 230 V and 15 kW
@ 400 V
Bit 1 = 0: Drive controller power does not exceed 30 kW @ 400 V or 15
kW @ 230 V)
Bit 1 = 1: Drive controller power exceeds 30 kW @ 400 V and 15 kW @
230 V
Bit 2 = 0: ATV58 Type H model
Bit 2 = 1: ATV58 Type FVC model
Bit 3 = 0: Overrating not allowed for lower power range model
Bit 3 = 1: Overrating allowed for lower power range model
(50/60 Hz switch on 60 Hz, caliber 3 kW @ 460 V to 15 kW @ 460 V,
and CFG = VT)
Bit 4 = 0: No extended VT ratings
Bit 4 = 1: Extended VT ratings
(ETI3 bit 3 = 1 and ORT = 1)

Monitoring Registers (Continued)

Word

Code

Description

Possible Values or Range