Line reactors, Three phase line reactors – Schneider Electric ALTIVAR 58 TRX User Manual
Page 160
Class 8839 58M Enclosed AC Drives
Three Phase Line Reactors
160
09/2003
©
2000–2003 Schneider Electric All Rights Reserved
The Class 8839 58M Enclosed AC Drives are
designed to operate from industrial power systems
with normal AC line conditions without the need of
additional line impedance from either an isolation
transformer or a line reactor. However, when
abnormal line conditions exist, additional line
impedance may be required. Typically, line reactors
are used to:
• Reduce the input rms current to the AC drive
ratings
• Lower the available fault current on high fault
distribution systems
• Limit the total harmonic voltage distortion from
the AC drive at the point of common coupling to
align with IEEE 519 guidelines
• Prevent AC drive nuisance tripping due to
transient overvoltages from power factor
correction capacitor switching
Line Reactors:
1. The line reactors are manufactured by
MTE, Inc.
2. Harmonic compensated up to 150% of
nominal current ratings
3. 5% nominal reactance
4. Refer to the following publications on the
subject of harmonics and benefits of drive
isolation transformers:
— 8803PD9402–Power Systems Harmonics–
Cause and Effects of AC Drives.
— 7460HO9501–Drive Isolation
Transformers-Application, Selection and
Specification Data
— 7460PD9501– Drive Isolation
Transformers–Solutions to Power Quality
HP Rating
208/230 VAC Line Reactor
Part No. (Integrated)
460 VAC Line Reactor
Part No. (Integrated)
Enclosed Standard Option
1
RL–01202
RL–00802
A10
2
RL–01202
RL–00802
A10
3
RL–01202
RL–00802
A10
5
RL–01801
RL–01203
A10
7.5
RL–01801
RL–01203
A10
10
RL–03501
RL–01802
A10
15
RL–03501
RL–01802
A10
20
RL–08001
RL–01802
A10
25
RL–08001
RL–03502
A10
30
RL–10001
RL–03502
A10
40
RL–10001
RL–03502
A10
50
RL–16002
RL–08002
A10
60
–
RL–08002
A10
75
–
RL–10002
A10
100
–
RL–13002
A10
125
–
RL–16013
A10
150
–
RL–20013
A10
200
–
RL–25013
A10
250
–
RL–32013
A10
300
–
RL–40013
A10
350
–
RL–50013
A10
400
–
RL–50013
A10
450
–
RL-60013
A10
500
–
RL-60013
A10