Siemens X-400 User Manual

Page 120

Advertising
background image

Technical Specifications

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches

120

C79000-G8976-C186-03

Interfaces

Load on the signaling contact

24 V DC / max. 100 mA safety extra-
low voltage (SELV)

Overcurrent protection at input

Non-replaceable fuse
(F 3.15 A / 250 V)

Digital Inputs

Input voltage:
• Rated value 24 V DC safety extra-

low voltage (SELV)

• For state "1“: + 13 V ...+ 30 V
• For state "0“: – 30 V... + 3 V
Max. input current: 8 mA
Max. cable length: 30 m
Inputs isolated from electronics.

C-Plug

Dimensions (width x height x depth)

24.3 x 17.0 x 8.1 mm

Weight

approx. 5 g

Power consumption

0.015 W

Memory capacity

32 Mbytes

Permitted Cable Lengths

TP cable length

With TP cord up to 10 m,
with FastConnect cabling system up to
100 m.

Cascading

Depth

Line/star structure

Any (only depending on signal propa-
gation time)

Ring with redundancy manager

50 (for reconfiguration time < 0.3 s)

Switching

Properties

Max. number of learnable addresses

8000

Aging time (default)

40 s

Switching procedure

Store and forward

Latency (store and forward time)

5 µs