Installation and commissioning, 1 installing / removing the scalance x414-3e – Siemens X-400 User Manual

Page 67

Advertising
background image

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches
C79000-G8976-C186-03

67

Installation and Commissioning

6

6.1

Installing / Removing the SCALANCE X414-3E

!

Warning
SCALANCE X-400 is designed for operation with safety extra-low voltage (SELV).
This means that only safety extra-low voltages (SELV) complying with
IEC950/EN60950/ VDE0805 can be connected to the power supply terminals.
The power supply unit for the 24 V DC supply must comply with NEC Class 2
(voltage range 20.4 - 28.8 V DC, current requirement max. 2 A). If the device is
supplied with power redundantly, both power supply units together must comply
with NEC Class 2.
Exceptions:

● Power supply with PELV (according to VDE 0100-410) is also possible if the

generated rated voltage does not exceed the voltage limits 25 V AC or 60 V
DC.

● Power supply by a SELV power source (according to IEC 60950) or PELV

power source (according to VDE 0100-410) without limited power is also per-
mitted if suitable fire protection measures are taken by:
- Installation in a cabinet or suitable enclosure
- Installation in a suitably equipped, closed room

!

Caution
The subject unit must be located in a Restricted Access Location where access
can only be gained by SERVICE PERSONNEL or by USERS who have been in-
structed about the reasons for the restrictions applied to the location and about any
precautions that shall be taken when operated in an air ambient of 50°C - 60°C

Advertising