Product Description of SCALANCE X-400

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches

46

C79000-G8976-C186-03

Startup Behavior

C-PLUG

X414-3E

Startup

1 not found

with internal configuration (if it exists)
or with factory defaults.

2 empty

with internal configuration, immediately
copies this automatically to the C-
PLUG.

3 written with own X414-3E configu-

ration data.

with C-PLUG configuration.

4 written with third-party X414-3E

configuration data.

with third-party C-PLUG configuration.

5 written with configuration data of a

different device type.

with internal configuration, red LED on
power module and log entry.

6 defective

with internal configuration, red LED on
power module and log entry.

In cases 1 and 2, the configuration data on the Switch CPU and the C-PLUG is
identical. In cases 3 and 5 the configuration data is different and can be synchro-
nized manually. In case 6, you can attempt to reformat the C-PLUG with the clean
function. If problems persist, replace the C-PLUG.

Notice
In case 4 (replacing the switch), the DIL switch settings of the C-PLUG and not the
physical switch settings are adopted. A deviation is signaled by the diagnostic op-
tions.

For more detailed information, refer to the SCALANCE X-400 Configuration Man-
ual

.