3 digital input connectors (x1) – Siemens X-400 User Manual

Page 92

Advertising
background image

Installation and Commissioning

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches

92

C79000-G8976-C186-03

6.6.3 Digital Input Connectors (X1)

Polarity Reversal Protection X1, X2

The two 5-pin male connectors (X1, X2) of the digital inputs 1 through 8 have no
polarity reversal protection. If the connectors are accidentally swapped over, this
does not cause damage or destroy circuits. In display modes A and C or B and D,
incorrect inputs are displayed during the time the connectors are swapped over.

Digital inputs 1 through 4 are connected using a 5-pin connector at the front termi-
nal block on the DI module.

X 2

X 1

I N 2

M 4

I N 3

I N 4

I N 1

Figure 6-11

Pin assignment of connector X1 (Inputs 1 through 4)

Conn. 1

IN1

Digital input 1

IN2

Digital input 2

M4

Ground

IN3

Digital input 3

IN4

Digital input 4

!

Warning
The input voltage must not exceed + 30 V and must not fall below – 30 V, other-
wise the DI module will be destroyed.

Advertising