Switch sw 1, Function description details, Example addresses = 1 to 64 – SMC Networks ProSoft 1560 User Manual

Page 11: Chapter 3 — hardware setup

Advertising
background image

11

Contents

Switch SW 1

Function

Description

Details

Datalink
Options

Host
PLC
Address
(when Global
Data Control
Enabled)

Allows the User to
select the level of
Datalink support the
1560-MBP unit will
have when talking to
the SCANport device.

Some devices do not
support Datalinks, in
which case the ‘No
Datalinks’ option must
be selected.

If the Global Data
Control is Enabled
(SW2-7 is set to 1)
then the 1560-MBP
must be told which
Host PLC Global
Database to get the
control values from.

To select the
appropriate Host,
determine the Host’s
Modbus Plus address
and select that
address using the dip
switches SW1- 1 to 6.

SW1-7 and 8

8

7

off off No Datalinks
off on Datalink A only
on off Datalink A&B only
on on Datalink A,B,C,D

SW1-1 to 6
1 Address Bit 0 Value = 1
2 Address Bit 1 Value = 2
3 Address Bit 2 Value = 4
4 Address Bit 3 Value = 8
5 Address Bit 4 Value = 16
6 Address Bit 5 Value = 32

Example Addresses = 1 to 64

6 5 4 3 2 1 Address
off off off

off

off

off

1

off off off

off

off

on

2

off off off

off

on

off

3

off off off

off

on

on

4

off off off

on

off

off

5

off off off

on

off

on

6

off off off

on

on

off

7

off off off

on

on

on

8

off off on off

off

off

9

off off on off

off

on

10

off off on off

on

off

11

off off on off

on

on

12

off off on on

off

off

13

off off on on

off

on

14

off off on on

on

off

15

off off on on

on

on

16

off on off

off

off

off

17

off on off

off

off

on

18

off on off

off

on

off

19

off on off

off

on

on

20

off on off

on

off

off

21

off on off

on

off

on

22

off on off

on

on

off

23

off on off

on

on

on

24

off on on off

off

off

25

off on on off

off

on

26

off on on off

on

off

27