Setting up the Adaptor I/O - Data In
Selects the parameters which will be made accessible for configuration/
writing from the 1560-MBP. As with the Data Out parameters, there are
eight possible selections. These may be chosen by the programmer to
meet the needs of the application.

Appendix B — Device Specific Hints

C1
C2
D1
D2

19

4

Maximum Frequency
Last fault

Logic Control Word
Since the most common implementation of the 1560-MBP is with the
variable speed drives, we have included the following table for the more
commonly used control bits. This word should be verified in the A-B
User Manual for the particular device being controlled.

Bit

Function

Description

0

Stop

1 = Stop, 0 = Not Stop

1

Start

1 = Start, 0 = Not Start

2

Jog

1 = Jog, 0 = Not Jog

3

Clear Faults

1 = Clear, 0 = Not Clear

4, 5

Direction

00 = No Command
01 = Forward
10 = Reverse
11 = Hold Direction

Drive Status Word
Since the most common implementation of the 1560-MBP is with the
variable speed drives, we have included the following table for the more
commonly used Status bits. This word should be verified in the A-B
User Manual for the particular device being monitored.

Bit

Function

Description

0

Enabled

1 = Enabled

1

Running

1 = Running

2

Cmd Direction

1 = Forward, 0 = Reverse

3

Actual Direction

1 = Forward, 0 = Reverse

4

Accel

1 = Accelerating

5

Decel

1 = Decellerating

6

Alarm

1 = Alarm Active

7

Fault

1 = Fault Active

8

At Speed

1 = At Speed