Appendix b, Device specific hints – SMC Networks ProSoft 1560 User Manual

Page 31

Advertising
background image

31

Contents

Appendix B

Device Specific Hints

SMC Dialogue Plus
The SMC Dialogue Plus does not support Datalinks, therefore the
configuration of SW1-7 and 8 should not include any of the Datalinks
Enabled. If a Datalink is enabled, the SCANport Status LED will toggle,
indicating an error in the SCANport communications.

The version of SMC which was tested (Rev 1.05) had 88 parameters.
Each parameter was accessible in the Modbus register listing shown in
Appendix A. Note that if one of the 88 parameters is to be changed from
a host that the host must enable the EEPROM Storage function by
writing a 2 into the Parameter Management parameter (Parameter 17 -
Modbus address 40117 ).

SMP 3
The SMP3 does not support Datalinks, therefore the configuration of
Datalinks should not include any of the Datalinks Enabled. If a Datalink
is enabled, the SCANport Status LED will toggle, indicating an error in
the SCANport communications.

The 1560-MBP is able to read all of the parameters out of the SMP3
unit.

Variable Speed Drives
In order to enable Frequency control from the 1560-MBP, the drive
parameter FREQUENCY SELECT 2 must be configured for the
appropriate Adapter ID representing the 1560-MBP module. This will
normally be Adaptor #2, unless a SCANport expander is being used (in
which case this Adaptor number will be based on the port the 1560-MBP
is plugged into).

Setting up the Adaptor I/O - Datalinks Out
Selects the parameter values which will be made available from
the 1560-MBP via Global Data Out. Placement of the values in
the 1560-MBP is referenced in Appendix A.

Appendix B — Device Specific Hints

Data Out

Image

Suggested

Parameter

Description

A1
A2

54

1

Output Power
DC Bus Voltage

B1
B2

23
53

Output Current
Output Volts