30 remarks – Sharp JW-20CM User Manual

Page 128

Advertising
background image

9

·

30

Remarks

From the previous page

Set whether the station number information should be output or not

· Set whether the station number information should be output or not on the parameter address

007763

(8)

.

007763

(8)

00

(H)

: Do not output

01

(H)

: Output

The station number information is output on the next

byte of the flag area (24 bytes.)

Whether the station
number information
should be output or not

V5

Set top address of flag area

File address: OCT (octal), word

File number/flag: HEX (hexadecimal), byte

· Set the top address of the flag area (24 bytes) in order to monitor the communication condition

and PC operation condition on the parameter address 007764 to 007767

(8)

.

· Flag area uses 24 bytes regardless number of connecting stations.

V5

007764

(8)

007765

(8)

007766

(8)

007767

(8)

Lower

Upper

File number

Output flag : ON

Do not output flag : OFF

D

7

Initial value

E0

(H)

01

(H)

00

(H)

80

(H)

Contents

01E0

(H)

000740

(8)

0740

File number 0

Output flag

Byte address

· The PC's input/output relays, auxiliary relays, registers etc. are all allocated individual byte

addresses for each item. However, the JW-20CM can assign these addresses with file

addressees allocated throughout the memory.

· The usable file numbers will vary with the memory module that is installed on the PC.

To the next page

e

l

u

d

o

m

y

r

o

m

e

m

f

o

e

m

a

N

s

r

e

b

m

u

n

e

li

f

e

l

b

a

s

U

H

A

M

1

-

W

J

,

A

M

1

-

W

Z

1

r

o

0

H

A

M

2

-

W

J

,

A

M

2

-

W

Z

1

r

o

0

H

A

M

3

-

W

J

,

A

M

3

-

W

Z

2

,

1

,

0

H

A

M

4

-

W

J

,

A

M

4

-

W

Z

7

,

6

,

5

,

4

,

3

,

2

,

1

,

0

I/O relay

Auxiliary relay

Latch relay

General purpose relay

TMR/CNT

time limited contact

TMR/CNT/MD

current value

File address

000377
000400

000677
000700
000777
001000

001577
001600

001777
002000

003777

Byte address

0000

00377
00400

00677
00700
00777
01000

01577

b0000

b17777

ZW model PCs

JW model PCs

Register

Register

File address

004000

004777
005000

005777
006000

015777

Byte address
09000

09777
19000

19777
29000

99777

ZW model PCs

JW model PCs

If file number is 1, file

address shall be within

000000 to 037777

(8)

.

(See page 13·20 and 21

for other cases.)

Advertising
This manual is related to the following products: