Rack no. slot no – Sharp JW-20CM User Manual

Page 88

Advertising
background image

8

·

50

(I/O error code of JW model)

• When error numbers 98 through 9C

(H)

occur, the module will store “rack No.” and “slot No.” in the

parameter address 005000

(8)

in the JW-20RS.

When more than one module has and error, the lowest “rack No.” and “slot No.” will be stored.

• A special I/O module error (9B

(H)

) can be detected by the JW-2DA/8AD/11DU/12DU/12PM. When

the JW-2DA/12PM detects this error, you can also assume that there is a problem in the 24 V

power supply.

• A fuse blown error (9C

(H)

) can be detected by JW-12S/13S/32S/33S/35S.

If the error cannot be eliminated after replacing the module in which the error occurred, check the

modules in the JW-20RS and then in the rack panel.

PC body and JW-20CM, JW-20RS

The operating status of the remote master station and slave stations will vary according to the

operation, stop, error, and power failure conditions in the PC as follows. For output hold switch in

detail, see page 8·15

When the JW-20RS fault lamp is lit and no error code is displayed, it might be the case that

the PC has stopped operation (in the program mode).

Parameter address D7 D6 D5 D4 D3 D2 D1 D0

005000

(8)

Rack No. Slot No.

Hold

Reset

Reset

Reset

Not fixed

Not Fixed

Condition of output module

Operating at normal

Stop at normal

Error

Remote master

station error

PC power in OFF

Close

Open

Open

Open

Open

SD RD CD

TEST FAULT S

0

to

S

7

JW-20RS Indication lamps

ERROR

COMM

PC body
operational
condition

Power supply

module

Halt

output

HALT

Power

lamp

POWER

Output hold

switch “HOLD”

Output hold switch

“RST”

Reset

Reset

Reset

Reset

Error
code

Error

code

Error
code

Operating at normal

Stop at normal

Error

Remote master

station error

Close

Open

Open

Open

SD RD CD

TEST FAULT S

0

to

S

7

JW-20CM Indication lamps

ON

ON

Not fixed

Not fixed

ERROR

COMM

PC body
operational
condition

Hold

Hold

Hold

Hold

Power supply

module

PC body

Halt

output

HALT

Power

lamp

POWER

Indicator

Operating

RUN

Error

FAULT

Flag

relay

System

memory

#170 to

#177

: Light ON, : Blinks, No mark: Lights OFF

80 40 20 10 8 4 2

Measure

Cause

Register I/O table

Replace the JW-20RS

Replace basic rack panel,

extension cable, I/O

module, or register I/O

table.

Replace the fuse

1

97

(H)

98

(H)

99

(H)

9A

(H)

9B

(H)

9C

(H)

Error

code

(HEX)

LED name

I/O table error

Input data parity error

Output data error

I/O table registration error

Special I/O module error

Blown fuse