(4) Voltage interruption time of slave module

The voltage interruption operation of slave module is carried out for service interruption signal (PF

signal) of power supply module, watchdog timer of slave module, and check 5 V power regardless of

setting voltage interruption time (#246) of master module.

· The PF signal of the power supply module goes “OFF” below

85% of the rated voltage.

· The watchdog timer of the slave module goes time-up in “320

ms.”

· When output hold switch is “RST,” the all halt output and output

module become “OFF” when communication with master station

have interruption of 320 ms.

· When the check of 5 V power is gone below 4.5 V, all are forced to reset. The power supply characteristics

varies according to the consumption current of the power supply module as following diagrams.

RST

Start

PF signal OFF

Communicating

at remote I/O

I/O processing of I/O module

Output hold

switch

Watchdog timer

time-up

5V power 4.5V max.

Halt output “open”

All output module “OFF”

End

Yes

Yes

Yes

Yes

No

No

No

No

No

Output hold time

Hold time [ms]

5.1V,7A load
(ZW-1PU)

5.1V,5A load
(ZW-2PU)

Output hold time

Hold time [ms]

100 VAC 50H input
(ZW-1PU)
24 VDC input
(ZW-2PU)

AC input voltage

DC input voltage

Load current [A]