4

(2) Communication timing

· For communication with slave stations, either of "synchronous" and "asynchronous" can be selected

for operation with the master station PC.

· When "synchronous" is selected, the JW-20CM communicates with synchronize with operation (one

scan) of the master station PC.

· When "asynchronous" is selected, the JW-20CM communicates with slave stations regardless of

operation of the master station PC. Therefore, even if communication of all stave stations is not

completed, the JW-20CM starts data exchange with the master station and PC.

SIO

RAM

RAM

RAM

ROM

ROM

CTC

CTC

Buffer
memory

PC

Interface

CPU

S

I

O

JW-20CM

Data
memory

Communication control port

Bus/interface port

Communication lines

Modem

Bus bonding

Communication

control

CPU

NO

YES

NO

YES

Processing of JW-20CM

Processing of PC side

Data exchange with

data memory

Remote I/O
communication processing

Communication

complete?

Check PC

hardware

Zero-cross

synchronization

I/O processing

Remote

communication

complete?

Data exchange with

remote I/O master

station RAM

PC operation

The slave station will not performs the zero-cross operation even if the master station PC is
“set zero-cross (zero-cross switch 07367 at OFF)”.