Particulate contamination – Lenovo 1047 User Manual

Page 127

Advertising
background image

Particulate contamination

Attention: Airborne particulates (including metal flakes or particles) and reactive gases acting alone or in
combination with other environmental factors such as humidity or temperature might pose a risk to the
server that is described in this document. Risks that are posed by the presence of excessive particulate
levels or concentrations of harmful gases include damage that might cause the server to malfunction or
cease functioning altogether. This specification sets forth limits for particulates and gases that are intended
to avoid such damage. The limits must not be viewed or used as definitive limits, because numerous
other factors, such as temperature or moisture content of the air, can influence the impact of particulates
or environmental corrosives and gaseous contaminant transfer. In the absence of specific limits that are
set forth in this document, you must implement practices that maintain particulate and gas levels that are
consistent with the protection of human health and safety. If Lenovo determines that the levels of particulates
or gases in your environment have caused damage to the server, Lenovo may condition provision of repair
or replacement of servers or parts on implementation of appropriate remedial measures to mitigate such
environmental contamination. Implementation of such remedial measures is a customer responsibility.

Table 30. Limits for particulates and gases

Contaminant

Limits

Particulate

• The room air must be continuously filtered with 40% atmospheric dust spot efficiency

(MERV 9) according to ASHRAE Standard 52.2

1

.

• Air that enters a data center must be filtered to 99.97% efficiency or greater, using

high-efficiency particulate air (HEPA) filters that meet MIL-STD-282.

• The deliquescent relative humidity of the particulate contamination must be more than 60%

2

.

• The room must be free of conductive contamination such as zinc whiskers.

Gaseous

• Copper: Class G1 as per ANSI/ISA 71.04-1985

3

• Silver: Corrosion rate of less than 300 Å in 30 days

1

ASHRAE 52.2-2008 - Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle

Size. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

2

The deliquescent relative humidity of particulate contamination is the relative humidity at which the dust absorbs

enough water to become wet and promote ionic conduction.

3

ANSI/ISA-71.04-1985. Environmental conditions for process measurement and control systems: Airborne

contaminants. Instrument Society of America, Research Triangle Park, North Carolina, U.S.A.

Important information for the European Directive 2002/96/EC

EU Only

The Waste Electrical and Electronic Equipment (WEEE) mark applies only to countries within the European
Union (EU) and Norway. Appliances are labeled in accordance with European Directive 2002/96/EC
concerning waste electrical and electronic equipment (WEEE). The Directive determines the framework for
the return and recycling of used appliances as applicable throughout the European Union. This label is
applied to various products to indicate that the product is not to be thrown away, but rather reclaimed upon

Appendix C. Notices

115

Advertising
This manual is related to the following products: