Installation and Commissioning

14

Figure 10 Bottom plate with cutouts

Cable and pipe openings must be sealed air-tight on completion of work.

5.4

Condensed Water Connection

If the XDK is operated below dew point, condensed water may occur. As standard there is a water con-

nection, 5/8" diameter, in the condensed water tray for drainage.

Preparations for Connecting

When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self-

filling siphon with return protection and that the condensate drain is properly sloped.
The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so

that air is not drawn into or blown out of the waste pipe.

Front

Condensed

Water Cutouts

Network

Cable

Entry

Sealed Cable Cutout

Rear

Cutout for

Water Pipes

Step 1):

Remove

the air

duct

Step 2):

Remove

the cap

Step 3.)

Connect the

nipple with a drain

hose 5/8"

Condensate

connection

Step 4.)

Move and snap the

nipple with hose

into the hole