0 servicing and maintenance, 1 general inspection on fans-annual, 1 fan replacement – Liebert Rack Enclosure With Integrated Water-Based Cooling XDK User Manual

Page 20: Figure 11 replacing a fan, Ervicing, Aintenance, General inspection on fans—annual, Fan replacement, Warning, Caution

Advertising
background image

Servicing and Maintenance

16

6.0

S

ERVICING

AND

M

AINTENANCE

6.1

General Inspection on Fans—Annual

• Check for unusual bearing noises. (Check for excessive bearing play.)

6.1.1 Fan Replacement

The expected service life is approximately 40,000 operating hours at a temperature of 40°C (104°F).
1. Remove the housing cover from the unit (with earth cable).
2. Determine which fan has failed.
3. Check the surface temperature of the fan and switch off the circuit breaker.
4. Disconnect supply cable at the fan terminal block.
5. Loosen the four fastening nuts for the fan to be replaced.
6. Remove the failed fan.

Figure 11 Replacing a fan

!

WARNING

Risk of high speed rotating fan blades. Can cause serious injury.
Disconnect all local and remote electric powers supplies and assure that fan blades have

stopped rotating before working within the unit.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within the unit.

!

CAUTION

Risk of explosive discharge of water under pressure. Can cause injury or equipment damage.
Shut off the water supply and relieve pressure before working with piping.

NOTE
Service and maintenance work must be performed only by properly trained personnel and in

accordance with applicable regulations as well as with manufacturers’ specifications.

NOTE
Use only original spare parts that have been tested and approved by the manufacturer. If

necessary, request a comprehensive spare parts list from the manufacturer. For cleaning, use

commercially available cleaning agents only. Follow the stipulated safety measures and do not

use any tools that may cause scratching or tools for scraping (surfaces will be irreversibly

damaged).

Step 3:

Disconnect

supply cable

at the fan

terminal

block

Step 4: Undo

the four

fastening

nuts

One of four

fastening nuts

Slot to

insert

wrench to

remove

nut

Advertising