Principle of Cooling Operation

Figure 2

Cooling airflow, side view

Air that has been heated by the servers to 95°F (35°C), for example, is circulated to a specially

designed air/water heat exchanger by high-performance fans. The heated air is cooled to 68-77°F

(20-25°C) and fed to the front of the server.
The server fans can draw in the air and feed it over internal components.
Cold water is provided by a separate Liebert XD Pumping unit.
A condensate tray with a 5/8" outlet is below the heat exchanger.

NOTE
If the rear door (with fans) is opened, the front door must be opened. If the front door is opened,

it is not necessary to open the rear door.

19" Equipment

Air / Water

Heat Exchanger

Cold Water Supply

Side of XDK

Rear
of
XDK

Front
of
XDK

Fan

Bank