Table 2 technical data, 1 data overview-xdk, Table 3 xdk general data – Liebert Rack Enclosure With Integrated Water-Based Cooling XDK User Manual

Page 9: Data overview—xdk, Table 2, Technical data, Table 3, Xdk general data

Advertising
background image

Description

5

3.2.1 Data Overview—XDK

Table 2

Technical data

Housing material

Aluminium sheet, sheet steel, galvanized and coated

Operating Temperature range

50°F to 95°F (10°C to 35°C)

Abs. atmospheric humidity

8g / kg maximum

Temperature difference across server

approx. 15K

Noise level

55 dB(A) sound pressure at a distance of 3 ft. (1m)

Useful load

2204 lb (1000kg)

Cold Water

Cooling capacity

17kW

Supply temperature

54°F (12°C) (other temperatures upon consultation)

Return temperature

64°F to 72°F (18°C to 22°C) (other temperatures upon consultation)

Max. operating pressure

145 PSI (10 bar)

Water supply connection

1"

Table 3

XDK general data

Nominal Cooling Capacity

17kW @ 54°F (12°C) EFT

Height, in (mm)

86.6 (2200)

Width, in (mm)

31.5 (800)

Depth, in (mm)

47 (1200)

Usable Height for Electronic

Equipment

40 U

Maximum Electronic

Equipment Depth, in (mm)

29 (740)

Electronic Equipment

Air Temperature, In/Out, °F (°C)

68/98 (20/37

Weight, Empty, lb (kg)

683 (310)

Maximum Weight, Filled

2,800 (1310)

Maximum Operating

Water Pressure, psi (bar)

145 (10)

Water Flow Rate, GPM (m

3

/h)

10.7 (2.44)

Water Pressure Drop, psi (bar)

10 (0.7)

Water Connections, in

1

Maximum Air Flow, CFM ( m

3

/h)

1800 (3,100)

Sound Pressure Level

55 dB(A) at 3 ft (1m)

Input Voltage

200-264 V, 1 ph, 50/60 Hz

Maximum Power Draw

1400W

Options

Leveling Feet or Casters

Advertising