Operating Conditions

2

2.0

O

PERATING

C

ONDITIONS

2.1

Proper Application

The XDK is a water-cooled enclosure and is intended for removing heat from electronic equipment

inside the cabinet. The cooling system in the cabinet is thermally independent of the room air. Water

is used to cool equipment installed in the XDK. No additional cooling of the server room is required.

NOTE
Under certain conditions, a small amount of heat, (approximately 0.5kW), can escape into the

room.

!

CAUTION

Risk of improper operation. Can cause equipment damage. For reliable function of the XDK,

cold water must be available in the correct amount, and at the correct temperature and

pressure. Observe water quality specified in VGB-R 455 P. (see 8.0 - Water Purity

Requirements ).

Table 1

General operating data

Ambient temperature

50°F to 95°F (10°C to 35°C)

(other temperatures upon request)

Absolute humidity in the installation location

8g H

2

O/ kg air maximum

Water temperature, supply

54°F (12°C); other temperatures upon request

Water temperature, return

64°F (18°C); other temperatures upon request

Water connection

from below

Condensed water connection

from below

Nominal voltage

200V to 264V (50Hz and 60 Hz)

Maximum operating pressure

145 PSI (10 bar)