Item

Specifications

Program method

Control method

Program memory

Program capacity

Operation processing speed

Basic instructions

Applied instructions

External inputs (X)

External outputs (Y)

Internal relay (R)

Special internal relay (R)

Link relay (L)

Timer/counter (T/C)

Data register (DT)

Link data register (LD)

Special data register (DT)

Index register (I0 to ID)

Master control relay (MCR)

Number of labels (LOOP)

Number of differentiations

Number of stepladders

Number of subroutines

Number of interruption programs

High-speed counter

*2

Pulse output

*3

Pulse catch input / interrupt input

Periodical interrupt

Potentiometer

Constant scan

Real-time clock

Flash ROM
backup

*6

Battery backup

Battery life

Password

Self-diagnosis function

Comment storage

PLC link function

Rewriting in RUN mode

Relay symbol method

Cyclic operation method

Flash ROM built-in (no battery backup required)

16k steps (C14), 32k steps (C30, C60)

Basic instruction 0.32

Ms/step

111

216

1760 points

*1

1760 points

*1

4096 points

192 points

2048 points

12285 words (C14), 32765 words (C30, C60)

256 words

374 words

14 words

256 points

256 labels

Up to program capacity

1000 stages

500 subroutines

Relay output type: 15 programs (14 external, 1 constant)

Transistor output type: 9 programs (8 external, 1 constant)

0.5ms to 30s

2 points (0 to 1000) (C14, C30) 4 points (0 to 1000) (C60)

Possible

Equipped (usable only when AFPX-MRTC is installed)

*4

Data register (32,765 words)

Counter 16 points (1008 to 1023), Internal relay 128 points

(R2470 to R255F), Data register 55 words

The memory allocated in the storage area by the

system register (only when a battery is installed)

*5

C14: 1230 days (actual operation 10 years at 25°C)

C30, C60: 990 days (actual operation 10 years at 25°C)

C14: 780 days (actual operation 10 years at 25°C)

C30, C60: 680 days (actual operation 10 years at 25°C)

(More than two batteries can be installed in C30 and C60.

In this case, the battery life is extended several times)

Capable (4 or 8 characters selectable)

Watch dog timer, program syntaxcheck

Capable (328KB) (backup battery not required)

Max. 16 units, link relay 1024 points, link register 128 words

(No data transfer or remote programming)

Capable

Backup by F12,
P13 commands
Auto-backup
at power failure

(when no power
is supplied)

After installing
AFPX-MRTC

Before installing
AFPX-MRTC

Built-in (Transistor output): single-phase 8ch (50kHz x 4ch + 10kHz x 4ch)

Built-in (Relay output): single-phase 8ch (10kHz x 8ch)

Pulse I/O cassette: single-phase 2ch (80kHz x 2ch)

Built-in (Transistor output): 100kHz x 2ch + 20kHz x 2ch

Pulse I/O cassette: One unit (one axis) 100kHz, or two units (two axes) 80kHz

Relay output type: Total 14 points (including the high-speed counter)

Transistor output type: Total 8 points (including the high-speed counter)

Total 1024 points: timer capable of counting

(1ms, 10ms, 100ms, 1s) x 32767

Counter capable of counting 1 to 32767

Notes:
*1 The actual usable number of points is restricted by the hardware.
*2 Specification at the rated input voltage of 24V DC, 25°C. Frequency may be lower due to the voltage and temperature.
*3 Max frequency may vary by the method of operation. Please refer to the manual for details.
*4 Calendar accuracy at 0°C: 119sec/month or less, 25°C: 51 sec/month or less, 55°C: 148 sec/month or less (Real-time clock requires a battery.)
*5 When data is stored in the storage area while the battery is not installed, the data is not cleared and the data value may be indefinite. The same condition occurs when the battery is exhausted.
*6 The number of possible rewrites is 10,000 or less.