Fp-x series, Specifications – Panasonic Programmable Controllers FP-X Series User Manual

Page 22

Advertising
background image

22

FP-X series

Input specifications (control unit, expansion unit and add-on cassette)

Relay output specifications (control units, expansion units)

Note:

*2

Please refer to the user manual for Y0 to Y7 of the transistor output type.

Item

Description

Insulation method

Output type

Rated load voltage

Load voltage allowable range

Max. load current

Max. inrush current

Output points per common

OFF state leakage current

ON state voltage drop

Response time

Voltage range for external power supply

Surge absorber

Operating indicator

Photocoupler

Open collector

1.5A

1

MA or less

Zener diode

LED display

Add-on cassette (AFPX-TR8, AFPX-TR6P, AFPX-IN4T3)

Control unit, Expansion unit

NPN type: 5 to 24VDC, PNP type: 24VDC

NPN type: 4.75 to 26.4VDC, PNP type: 21.6 to 26.4VDC

0.5A

24VDC

21.6 to 26.4VDC

NPN type: 0.3A, PNP type: 0.5A

TR8: 8 points/common, TR6P: 6 points/common, IN4T3: 3 points/common

1.5VDC or less

0.1ms or less

0.8ms or less

0.3VDC or less

1ms or less*

2

1ms or less*

2

21.6 to 26.4VDC

C14: 6 points/common, E16: 8 points/common, C30, C60, E30: 8 or 6 points/common

OFF

m ON

OFF

m ON

Transistor output specifications (Control unit, expansion unit and add-on cassette)

Specifications

Item

Description

Insulation method

Rated input voltage

Operating voltage range

Rated input current

Input points per common

Min. ON voltage/ON current

Max. OFF voltage/OFF current

Input impedance

Response

time

Operating indicator

Photocoupler

24VDC

21.6 to 26.4VDC

(Input power polarity either positive or negative)

Same as above

LED display

Note:

*1

Specification at the rated input voltage of 24VDC, 25°C.

Control unit X0 to X7

0.6ms or less: Normal input
50

Ms or less: High-speed counter, pulse catch,

interruption input setting *

1

Control unit X8 and after, Expansion unit

0.6ms or less

Control unit X0 to X3

135

Ms or less: Nominal input

5

Ms or less: High-speed counter, pulse catch,

interruption input setting*

1

Control unit X4 to X7

135

Ms or less: Nominal input

50

Ms or less: High-speed counter, pulse catch,

interruption input setting*

1

Control unit X8 and after, Expansion unit

0.6ms or less

19.2V/3 mA

2.4V/1 mA

Approx. 5.1k

7 (Control unit X0 to X7)

Approx. 5.6k

7 (Control unit X8 and after, Expansion unit)

19.2V/6mA (Control unit X0 to X3)

19.2V/3mA (Control unit X4 and after, Expansion unit)

2.4V/1.3mA (Control unit X0 to X3)

2.4V/1mA (Control unit X4 and after, Expansion unit)

Approx. 3k

7 (Control unit X0 to X3)

Approx. 5.1k

7 (Control unit X4 to X7)

Approx. 5.6k

7 (Control unit X8 and after, Expansion unit)

Approx. 4.7mA (Control unit X0 to X7)

Approx 4.3mA (Control unit X8 and after, Expansion unit)

Approx. 8mA (Control unit X0 to X3)

Approx. 4.7mA (Control unit X4 to X7)

Approx. 4.3mA (Control unit X8 and after, Expansion unit)

Approx. 3.5mA

1.0ms or less

1.0ms or less

8 points/common (C14, E16) 16 points/common (C30, C60, E30)

8 points/common (AFPX-IN8), 4 points/common (AFPX-IN4T3)

19.2V/3mA

2.4V/1mA

Approx. 6.8k

7

Relay output (control unit and expansion unit)

Transistor output (control unit and expansion unit)

Add-on cassette (AFPX-IN8, AFPX-IN4T3)

OFF

m ON

OFF

m ON

Item

Description

Output type

Rated control capacity (Resistive load)

Output points per common

Response time

Life time

Surge absorber

Operating indicator

1a contact

2A 250VAC, 2A 30VDC (8A or less/common)

C14, E16: 1 point or 3 points/common, C30, E30: 1 point or 4 points/common, C60: 1, 2 or 4 points/common

Approx. 10ms

Approx. 8ms

20 million operations or more (Operation frequency 180 times/min)

100,000 operations or more (Operation frequency 20 times/min at the rated control capacity)

None

LED display

Mechanical

Electrical

OFF

mON

ON

mOFF

01/2008

Advertising