Tool port

Tool port

Tool port

Ethernet

RS232C

Measuring
instrument

Measuring
instrument

Measuring
instrument

Touch
panel

Touch
panel

Touch
panel

Operation data managing software
PCWAY

RS232C

RS232C

Ethernet

Internet connection

Ethernet

Programming software
FPWIN GR
FPWIN Pro

9

This Ethernet cassette fulfills user requiremens such as the “easy collection of inspection/

production data” or “remote changing of ladder programs”, using LAN (Ethernet).

Data collection

Remote maintenance

Enables easy Ethernet connections with a compact PLC, which were previously not possible.
Also equipped with an RS232C port. Together with the tool port (programming port), a total of 3
communication ports are available, which is remarkable for a compact PLC.
For example, the following operations are simultaneously available with this cassette attached:

1. I/O control
2. Reading data from a tester (measuring instrument) of inspection equipment (RS232C)
3. Collecting the read data from the host computer (Ethernet)
4. Setting/monitoring via a touch panel (Tool port)


Program / monitoring

*1: In Japan, as of May 1, 2007

AFPX-COM5

Ethernet

RS232C

The industry’s first*¹ add-on to equip a compact PLC with an Ethernet port

Application

Interface

Specifications and functions

Ethernet

(COM1)

10BASE-T, 100BASE-TX, TCP/IP, Baud rate: 9600bps/115200bps

MEWTOCOL-COM master/slave (3 connections max.)

General- purpose serial communications (1 connection max.)

Server function, client function

RS232C

(COM2)

3-wire (RD, SD, SG), Asynchronous,

Baud rate: 300bps to 115200bps

MEWTOCOL-COM master/slave

General-purpose serial communications

Modbus-RTU master/slave

Ethernet port

functions

Specifications

MEWTOCOL-COM

master/slave

Automatically sends responses without communica-

tion programs to commands of Matsushita’s open

protocol “MEWTOCOL”.

Contact/word data writing/reading, program editing

PCWAY, FPWIN GR and FPWIN Pro are supported.

General

purpose

serial

communi-

cations

Server

function

Waits for a connection from a client PC (personal

computer), and after the connection has been estab-

lished, receives data from the PC.

Client

function

After the power has been turned on, establishes a

connection to a preset IP address and sends data.

Use our free software “Configurator WD” for setting up
the Ethernet port (e.g. IP address and operation mode).

Download the software free of charge from:
http://www.panasonic-electric-works.com