Powerware 9 User Manual
Page 10

Introduction
4
Powerware
®
9 Prestige Series User’s Guide (600 VA - 1800 VA)
:
www.powerware.com
Prestige 600 - 1500 VA, 120V Models
Load
(VA) at
Load
Internal UPS Batteries (Rounded to the Nearest Minute)
(VA) at
.7 PF*
Load
(W)
650
800
1000
750 EXT
1000 EXT
1250 EXT
1500 EXT
200
140
37
37
37
68
68
68
68
400
280
22
22
22
32
32
32
32
600
420
12
12
12
20
20
20
20
800
560
8
8
15
A
14
14
14
1000
700
6
11
11
11
1250
875
8
8
1500
1050
6
Load
Load
External Battery Cabinet Configurations for EXT Models
Load
(VA) at
.7 PF*
Load
(W)
1/2
Cabinet
1
Cabinet
1 1/2
Cabinets
2
Cabinets
2 1/2
Cabinets
3
Cabinets
3 1/2
Cabinets
4
Cabinets
200
140
143
216
290
364
438
513
589
663
400
280
69
115
158
198
239
280
320
362
600
420
43
73
105
137
165
194
221
249
750
525
33
56
80
106
134
156
178
202
1000
700
23
39
57
75
95
114
135
151
1250
875
17
30
42
56
70
86
102
118
1500
1050
14
23
32
43
55
67
78
91
*
Typical Power Factor (PF);
A