41

Powerware

®

9 Prestige Series User’s Guide (600 VA - 1800 VA)

:

www.powerware.com

Using Maintenance Bypass

Use the following procedure to transfer the critical load to Maintenance
Bypass (AC Line operation) and remove the UPS:

1. Disconnect the DB-25 serial communications cable from the

serial port on the UPS rear panel.

2. Toggle the Bypass switch on the PowerPass to the BYPASS

position (see Figure 13 or Figure 14). The PowerPass is now
powering your equipment from utility power.

3. Press and hold the Output

Off button until the long beep

ceases (approximately three seconds). The



indicator

remains lit.

4. Switch the circuit breaker on all battery cabinets to the

OFF (O) position.

5. Disconnect the battery connector on the UPS rear panel.

6. Using a #2-Phillips screwdriver, loosen the PowerPass

mounting screw until it is free (the screw remains captive).

7. Remove the PowerPass from the UPS, being careful not to

loosen the power cords plugged into the PowerPass.

Laser Printer

UPS Load

PowerPass

Utility Power

Figure 12. PowerPass Block Diagram (AC Line Operation)