Powerware 9 User Manual
Page 11
Advertising

Introduction
5
Powerware
®
9 Prestige Series User’s Guide (600 VA - 1800 VA)
:
www.powerware.com
Prestige 600 - 1250 VA, 208 - 240V Models
Load
(VA)
Load
Internal UPS Batteries (Rounded to the Nearest Minute)
(VA)
at
.7 PF*
Load
(W)
600
800
1000
800
EXT
1000
EXT
1250
EXT
200
140
33
33
33
56
56
56
400
280
21
21
21
29
29
29
600
420
11
11
11
19
19
19
800
560
7
7
13
13
13
1000
700
6
10
10
1250
875
8
Load
(VA)
Load
External Battery Cabinet Configurations for EXT Models
(VA)
at
.7 PF*
Load
(W)
1/2
Cabinet
1
Cabinet
1 1/2
Cabinets
2
Cabinets
2 1/2
Cabinets
3
Cabinets
3 1/2
Cabinets
4
Cabinets
200
140
133
203
274
346
418
491
564
637
400
280
70
117
159
201
243
285
328
371
600
420
46
76
110
141
171
200
230
260
800
560
33
55
79
105
132
153
176
199
1000
700
25
42
61
81
102
124
147
161
1250
875
19
32
46
61
77
94
111
129
*
Typical Power Factor (PF)
Advertising