Powerware 9 User Manual

Page 11

Advertising
background image

Introduction

5

Powerware

®

9 Prestige Series User’s Guide (600 VA - 1800 VA)

:

www.powerware.com

Prestige 600 - 1250 VA, 208 - 240V Models

Load

(VA)

Load

Internal UPS Batteries (Rounded to the Nearest Minute)

(VA)

at

.7 PF*

Load

(W)

600

800

1000

800

EXT

1000

EXT

1250

EXT

200

140

33

33

33

56

56

56

400

280

21

21

21

29

29

29

600

420

11

11

11

19

19

19

800

560

7

7

13

13

13

1000

700

6

10

10

1250

875

8

Load

(VA)

Load

External Battery Cabinet Configurations for EXT Models

(VA)

at

.7 PF*

Load

(W)

1/2

Cabinet

1

Cabinet

1 1/2

Cabinets

2

Cabinets

2 1/2

Cabinets

3

Cabinets

3 1/2

Cabinets

4

Cabinets

200

140

133

203

274

346

418

491

564

637

400

280

70

117

159

201

243

285

328

371

600

420

46

76

110

141

171

200

230

260

800

560

33

55

79

105

132

153

176

199

1000

700

25

42

61

81

102

124

147

161

1250

875

19

32

46

61

77

94

111

129

*

Typical Power Factor (PF)

Advertising