Powerware 9 User Manual

Page 12

Advertising
background image

Introduction

6

Powerware

®

9 Prestige Series User’s Guide (600 VA - 1800 VA)

:

www.powerware.com

Prestige 1500 - 1800 VA, 208 - 240V Models

Load

UPS with External Battery Cabinet Configurations (Rounded to the Nearest Minute)

Load

(VA)

at

.7 PF*

Load

(W)

Internal

UPS

Battery

1/2

Cabinet

1

Cabinet

1 1/2

Cabinets

2

Cabinets

2 1/2

Cabinets

3

Cabinets

3 1/2

Cabinets

4

Cabinets

200

140

59

128

194

260

327

393

460

527

595

400

280

29

64

107

149

186

224

263

302

339

600

420

19

42

71

102

135

161

189

217

244

800

560

14

32

52

76

100

125

148

169

191

1000

700

11

24

41

59

77

98

119

138

156

1250

900

8

19

32

45

59

76

92

108

125

1500

1050

7

14

25

36

48

60

73

86

101

1800

1200

5

12

20

29

38

48

59

69

80

*

Typical Power Factor (PF)