Powerware 9125 Two-in-One UPS 2500 User Manual

Page 67

Advertising
background image

SPECIFICATIONS

EATON Powerware

®

9125 Two-in-One UPS (2500/3000 VA) User’s Guide

S 164201374 Rev D

www.powerware.com

61

Table 7. Weights and Dimensions

UPS

Extended Battery Module

Dimensions
(WxDxH)

43.2

Ч

60.7

Ч

8.9 cm

17.0”

Ч

23.9”

Ч

3.5” (2U)

43.2

Ч

60.7

Ч

8.9 cm

17.0”

Ч

23.9”

Ч

3.5” (2U)

Weights

37 kg (81.5 lb)

42.5 kg (93 lb)

Table 8. Environmental and Safety

120V Models

208V Models

230V Models

Operating Temperature

0°C to 40°C (32°F to 104°F)

Optimal battery performance: 25°C (77°F)

Storage Temperature

0°C to 25°C (32°F to 77°F)

Transit Temperature

-25°C to 55°C (-13°F to 131°F)

Relative Humidity

5–95% noncondensing

Operating Altitude

Up to 3,000 meters above sea level

Transit Altitude

Up to 10,000 meters above sea level

Audible Noise

Less than 45 dBA Normal mode, typical load

Less than 50 dBA Battery mode

Surge Suppression

IEEE C62.41 Category B

IEEE C62.41 Category B

IEC 61000-4-5

IEC 61000-4-5

Safety Conformance

UL 1778, UL 497A

CSA C22.2, No. 107.1, 107.2

NOM-019-SCFI

UL 1778, UL 497A

NOM-019-SCFI

IEC 60950-1; EN 62040-1-1

IEC 60950-1; EN 62040-1-1

Agency Markings

cULus, NOM-NYCE

cULus, NOM-NYCE, CE,

TÜV-GS (G models only)

CE, TÜV-GS

EMC (Class A)

FCC Part 15, ICES-003

FCC Part 15, ICES-003

EN 50091-2, IEC 62040-2

Advertising