Powerware 9125 Two-in-One UPS 2500 User Manual

Page 68

Advertising
background image

SPECIFICATIONS

EATON Powerware

®

9125 Two-in-One UPS (2500/3000 VA) User’s Guide

S 164201374 Rev D

www.powerware.com

62

Table 9. Battery

UPS Configuration

(6) 12V, 9 Ah internal batteries

EBM Configuration

PW9125 72 EBM: (12) 12V, 9 Ah (2 strings of 6 batteries in parallel)

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

Internal battery: approximately 3 hours to 90% usable capacity at nominal line voltage

after full load discharge

External battery: no more than 20x discharge time to 90% usable capacity at nominal line

voltage after full load discharge

Monitoring

Advanced monitoring for earlier failure detection and warning; auto detection of

additional EBMs

Table 10. Battery Runtimes (in Minutes at Full/Half Load)

Model

UPS Internal Batteries

1 EBM

2 EBMs

3 EBMs

4 EBMs

2500 VA/1750W

7/16

28/57

48/90

68/150

88/200

3000 VA/2100W

5/13

25/55

38/72

54/120

70/160

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

Advertising