Increasing Current Drive

Each channel of the NI 9472 has a continuous output current of
0.75 A, and each channel of the NI 9474 has a continuous output
current of 1 A. If you want to increase the output current to a
device, you can connect any number of channels together in
parallel. For example, using the NI 9474, if you want to drive 4 A
of current, connect DO<0...3> in parallel as shown in Figure 4.
You must turn all parallel channels on and off simultaneously so
that the current on any single channel cannot exceed the 1 A rating.

Figure 4. Increasing the Current to a Device Connected to the NI 9474

NI 9474

DO3

DO1

DO0

DO2

4 A

+

_

COM

1 A

1 A

1 A

1 A

External
Power
Supply