Nx Networks NX series User Manual

Page 39

Advertising
background image

Cabling and connections

39(86)

6

6.1.3

Cable installation and the UL standards

To meet the UL (

Underwriters Laboratories

) regulations, a UL-approved copper cable with a

minimum heat-resistance of +60/75

°

C must be used.

The tightening torques of the terminals are given in Table 6-4.

Type

Frame

Tightening torque

[Nm]

Tightening torque

in-lbs.

NX5 0003—0012

FR4

0.5—0.6

4—5

NX5 0016—0031

FR5

1.2—1.5

10—13

NX5 0038—0061

FR6

4

35

NX5 0072—0105

FR7

10

85

NX5 0140

FR8

20/9*

170/76*

NX5 0168—0205

FR8

40/22*

340/187*

Table 6-4. Tightening torques of terminals

* Tightening torque of terminal connection to the isolative base in Nm/in-lbs.

6.1.4

Cable and motor insulation checks

1. Motor cable insulation checks

Disconnect the motor cable from terminals U, V and W of the frequency converter and from the
motor. Measure the insulation resistance of the motor cable between each phase conductor as
well as between each phase conductor and the protective ground conductor.

The insulation resistance must be >1M

.

2. Mains cable insulation checks

Disconnect the motor cable from terminals L1, L2 and L3 of the frequency converter and from
the mains. Measure the insulation resistance of the motor cable between each phase
conductor as well as between each phase conductor and the protective ground conductor.

The insulation resistance must be >1M

.

3. Motor insulation checks

Disconnect the motor cable from the motor and open the bridging connections in the motor
connection box. Measure the insulation resistance of each motor winding. The measurement
voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation
resistance must be >1M

.

Advertising