Connected not conn, Connected, Continuous – Nx Networks NX series User Manual

Page 70: Continuous temperature

Advertising
background image

70(86)

Control keypad

7

Figure 7-13. Internal brake resistor connection

Fan control (P6.3.4)

This function allows the control of the frequency converter’s cooling fan. When the power is
switched on the fan can be set to run continuously or dependant on the temperature of the unit. If
the latter function has been selected the fan is switched on automatically when the heat sink
temperature reaches 60

°

C. The fan receives a stop command when the heat sink temperature

falls to 55

°

C. However the fan runs for about a minute after receiving the stop command, as well

as after changing the value from Continuous to Temperature.

Enter the edit mode by pushing the

right arrow menu button

. The present mode shown starts to

blink. Use the

Browser buttons

to change the fan mode. Accept the change with the

Enter button

or return to the previous level with the

left arrow menu button

.

Figure 7-14. Fan control function

HMI acknowledge timeout (P6.3.6)

This function allows the user to change the timeout of the HMI acknowledgement time.

Note! If the frequency converter has been connected to the PC with a normal cable, the default
values of parametres 6.3.6 and 6.3.7 (200 and 5) must not be changed.
If the frequency converter has been connected to the PC via a modem and there is a delay in
transferring messages, the value of par. 6.3.6 must be set according to the delay as follows:

S1

"

S9

READY

I/Ot erm

READY

I/Ot erm

READY

I/Ot erm

enter

READY

I/Ot erm

I/Ot erm

P1

"

P7

System Menu

System settings

InternBrakeRes

Connected

Not conn.

InternBrakeRes

Connected

InternBrakeRes

READY

I/O term

READY

I/O term

enter

READY

I/O term

Fan control

Continuous

Fan control

Fan control

Continuous

Temperature

OR:

Advertising