Fault tracing

9

9. FAULT

TRACING

When a fault is detected by the frequency converter control electronics, the drive is stopped and
the symbol F together with the ordinal number of the fault, the fault code and a short fault
description appear on the display. The fault can be reset with the

Reset button

on the control

keypad or via the I/O terminal. The faults are stored in the Fault history menu (M5) which can be
browsed. The different fault codes can be found in the table below.

The fault codes, their causes and correcting actions are presented in the table below. The
shadowed faults are A faults only. The faults written in white on black background may appear as
both A and F fault.

Fault
code

Fault

Possible cause

Correcting measures

1

Overcurrent

Frequency converter has detected too
high a current (>4*I

n

) in the motor cable:

sudden heavy load increase

short circuit in motor cables

unsuitable

motor

Check loading.
Check motor size.
Check cables.

2

Overvoltage

The DC-link voltage has exceeded the
limits defined in Table 4-1.

too short a deceleration time

high overvoltage spikes in utility

Make the deceleration time longer.

3

Earth fault

Current measurement has detected that
the sum of motor phase current is not
zero.

insulation failure in cables or motor

Check motor cables and motor.

5

Charging switch

The charging switch is open, when the
START command has been given.

faulty

operation

component

failure

Reset the fault

and restart.

Should the fault re-occur, contact your
nearest distributor.

6

Emergency
stop

Stop signal has been given from the
option board.

7

Saturation trip

Very high overload
Defective component

Cannot be reset from the keypad.
Switch off power. If this does not help
contact your nearest distributor.

8

System fault

The frequency converter troubleshooting
system is unable to locate the fault.

Reset the fault

and restart.

Should the fault re-occur, contact your
nearest distributor,

9

Undervoltage

DC-link voltage is under the voltage limits
defined in.

most probable cause: too low a
supply voltage

frequency converter internal fault

In case of temporary supply voltage

break reset the fault

and restart

the frequency converter. Check the
supply voltage. If it is adequate, an
internal failure has occurred.
Contact your nearest distributor..

10

Input line
supervision

Input line phase is missing.

Check supply voltage and cable.

11

Output phase
supervision

Current measurement has detected that
there is no current in one motor phase.

Check motor cable and motor.

12

Brake chopper
supervision

no brake resistor installed

brake resistor is broken

brake chopper failure

Check brake resistor.
If the resistor is ok, the chopper is faulty.
Contactyour nearest distributor.

13

Frequency
converter
under-
temperature

Heatsink temperature is under –10

°

C